FMR-7036 | Fire Annunciator Keypad | 5.0 
Setting the FMR-7036 Address 
 
 
Bosch Security Systems, Inc. | 9/08 | F01U010584-01
Figure 3: 
Mounting Hole Locations 
Back of FMR-7036 Keypad
1
2
2
3
3
3
3
4
1 -  Holding tabs for reference guides 
2 -  Release tab 
3 -  Mounting Hole 
4 -  Wire Entrance 
 
 
 
 
Do not secure the base at this point. 
 
Figure 4: 
Inside View of FMR-7036 Keypad 
1
8
Green
Yellow
Black
Red
Connector Cable Orientation
1
2
3
4
5
3
6
7
8
1 -  Wire Entrance 
2 -  Internal Sounder 
3 -  Mounting Hole 
4 -  Address jumper pins 
5 -  Control Keys 
6 -  Reset switch 
7 -  2-line 16-character display 
8 -  Lock 
 
5.0  Setting the FMR-7036 
Address 
 
Each keypad must have its address set 
with its address pins. The keypads must 
also be programmed at the control panel. 
 
Figure 5: 
FMR-7036 Address Jumper Settings 
Address 1
Address 4
Address 7
Address 10
Address 13
Address 2
Address 5
Address 8
Address 11
Address 14
Address 3
Address 6
Address 9
Address 12
Do not use
address 15
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
1 2
4
8
3
5 6 7
Select the keypad address (1-14). 
Place the shorting jumpers over the address pins as 
shown in Figure 5
 
Each option bus device must have its own 
address, and each address can only 
support one device. 
6.0  Wiring the FMR-7036 
 
Be sure all wiring is un-powered before 
routing. Keypad wiring cannot be run with 
smoke detector wiring, NAC wiring or MUX 
loop wiring. 
For the FPD-7024 FACP, the maximum allowed DC 
current draw from the auxiliary power is 500 mA for 
keypads. The maximum length of wire (all branches 
added together) that can be connected to the option 
bus terminals is 4000 ft (1,219 m). 
The maximum length between any one device and 
the panel terminals depends on the current drawn 
on the branch that the device is on. The current 
draw on a particular branch can be found by adding 
together the individual current draws of each device 
connected to the branch. 
Refer to the FPD-7024 Installation Guide  
(P/N: F01U008458)
 for detailed wire length 
calculations.