Bosch FMR-7036 User Manual

Page of 8
FMR-7036 | Fire Annunciator Keypad | 8.0 
FMR-7036 Operation 
 
 
Bosch Security Systems, Inc. | 9/08 | F01U010584-01
8.2 Reset 
The Reset key is used to reset the control panel after 
an alarm has occurred. Any sounders or NACs that 
are activated will silence, and smoke detector zones 
will remove power briefly to reset detectors. 
 
The Reset key causes the FMR-7036 to transmit a 
hard coded passcode of 9753 followed by the Reset 
key normally found on the FMR-7036. The control 
must be programmed to accept this code before the 
FMR-7036 will work (refer to Section 7.0 on page 5 
of this installation guide). 
8.3 Scrolling 
Buttons 
The scrolling keys are used to view off-normal 
conditions. The second line of the display will 
alternate between the text of the event and the 
instructions of which arrow button to press. 
If the control panel is configured so that it requires 
remote keypads to enter a pin, the bottom line of 
the display will read Please Enter Pin. 
To operate, unlock keyswitch and wait for the 
second line to change to Use ACK/FUNC Key. 
Press Silence, Reset, or ►. 
If a pin is not required the display will show Use 
ACK/FUNC Key. 
To operate, unlock keyswitch 
and press Silence, Reset, or ►. 
The ► is used as the Acknowledge button. When 
pressed, the keypad and control panel  peizo will silence 
but the NACs will not be affected. 
Pressing the ► key allows you to step through the 
groups of off-normal conditions. 
Pressing the ▲ or ▼ allows you to view details of an 
off-normal condition within the group selected. 
Pressing the ◄ key returns you to the main menu. If 
pressed again, it releases control of the panel. If this 
is not done, it will automatically time out in 3 min. 
8.4 Keylock 
Switch 
The Keylock Switch is an extra security feature built 
into the FMR-7036 in accordance with NFPA 72 
requirements. It can be used to lock out the 
annunciator to prevent unwanted silence or resetting 
of the control panel. 
 
Using the Keylock Switch to lockout the 
FMR-7036 will prevent any user from 
silencing or resetting alarms, including 
emergency personnel such as the police or 
fire department. Check with the local 
Authority Having Jurisdiction before using 
this feature. 
Turn the Keylock Switch to Lock to prevent 
unwanted use of the Silence, Reset, and scrolling 
buttons. 
Turn the Keylock Switch to Unlock to restore 
normal operation of the Silence, Reset, and scrolling 
buttons. 
 
The key may only be removed in the locked 
position. 
8.5 Display 
The two-line, 16-character display is capable of 
showing all messages normally displayed on a FPD-
7024 or FMR-7033 keypad. All alarm and status 
messages are included. In addition, there are four 
LEDs for easy reading of annunciator status from a 
distance. Refer to Table 1 for a description of each 
LED’s function. 
Table 1:  
FMR-7036 LED Functions 
 
 
 
LED Color 
Function 
Supervisory 
Yellow 
Turns on for any supervisory 
condition 
Alarm 
Red 
Turns on for any fire alarm, 
including water flow  
Trouble 
Yellow 
Turns on for any trouble 
conditions at the control panel. 
Read the LCD display on the 
FMR-7036 for detailed Trouble 
information. 
Silence 
Yellow 
Turns on whenever the  Silence 
button is activated. 
8.6 Reset 
Switch 
Use the Reset Switch to reset the keypad if the 
display freezes or shows garbage, or if the Panel 
Reset function does not resolve the problem.