Bosch D625 User Manual

Page of 48
D623 Series/D625 Series | User's Guide | Control Panel Event Descriptions 
 
Bosch Security Systems | 9/04 | 46841E 
33 
 
Control Panel Event Descriptions 
The following table lists the events generated by the 
control panel
. These events appear in the 
control panel
 log by 
name and in the pager display by event number. 
Table 8:  Control Panel Event Descriptions 
 
Event # 
Event 
Description 
Event # 
Event 
Description 
01 
AC Fail 
AC power to control panel 
interrupted. 
24 
Rstrl Batt Low 
Battery restoral from low battery. 
02 
AC Restore 
AC power to control panel 
restored. 
25 Rstrl 
Batt 
Missing 
Battery restoral from missing 
battery. 
03 
Alarm, 
Tamper 
Alarm from detection device 
tampered with. 
26 
Bypass, Fire, 
User 
Selective bypass by user of fire 
detection device. 
04 Alarm, 
Emergency 
Alarm from emergency detection 
device or ABC key programmed 
for emergency response. 
27 Bypass, 
Fire, 
RAM IV 
Selective bypass of fire detection 
device by RAM IV. 
05 
Alarm, Panic 
Alarm from panic/emergency 
detection device. 
28 
Bypass, Ctrl, 
User 
Selective bypass by user of 
controlled detection device. 
06 Alarm, 
Invisible 
Alarm from detection device that 
does not appear at keypad during 
alarm or trouble conditions. 
29 Bypass, 
Ctrl, 
RAM IV 
Selective bypass by RAM IV of 
controlled detection device. 
07 
Alarm, 
24-hr. Burg 
Alarm from burglary detection 
device on 24 hours per day. 
30 
Bypass, 24-hr, 
User 
Selective bypass by user of 24-hr. 
non-fire detection device. 
08 Alarm, 
Cntrl, 
Dly 
Alarm from detection device with 
entry/exit delays. 
31 Bypass, 
24-
hr., RAM IV 
Selective bypass by RAM IV of 24-
hr. non-fire detection device. 
09 
Alarm, 
Cntrl 
Alarm from detection device such 
as keyswitches, motion detectors 
(followers), or devices that initiate 
an alarm immediately (do not follow 
any entry/exit delays). 
32 
Bypass, 
Forced Pt 
Detection device force-armed 
10 Cross, 
Tamper 
Tamper alarm from detection 
device with Cross Point option 
selected. 
33 Bypass, 
Swinger 
Point swinger bypassed. 
11 
Cross, 
Emergency 
Emergency alarm from detection 
device with Cross Point option 
selected. 
34 
UnBypass, 
Fire, Usr 
User cleared bypass (unbypass) of 
fire detection device. 
12 
Cross, Panic 
Panic alarm from detection device 
with Cross Point option selected. 
35 UnBypass, 
Ctrl, Usr 
User cleared bypass (unbypass) of 
controlled detection device. 
13 
Cross, 
Invisible 
Panic alarm from invisible detection 
device with Cross Point option 
selected. 
36 
UnBypass, 
24-hr., Usr 
User cleared bypass (unbypass) of 
24-hr. detection device. 
14 Cross, 
24-hr. Burg 
Burglary alarm from detection 
device with Cross Point option 
selected. 
37 Call 
For 
Service 
Report sent automatically at Call 
For Service interval. Does not 
indicate a trouble condition. 
15 
Cross, Cntrl, 
Dly 
Alarm from entry/exit detection 
device with Cross Point option 
selected. 
38 
Cancel Alarm 
User acknowledged active alarm 
before bell time expired for non-fire 
detection device. 
16 Cross, 
Cntrl 
Alarm from keyswitch, follower, or 
instant detection device with Cross 
Point option selected. 
39 
Cancel Fire 
User acknowledged active alarm 
before bell time expired for fire 
detection device. 
17 
Cross, 
Unverified 
Fault on one non-fire point type 
with Cross Point option selected. 
This is not an alarm event. 
40 
CheckSum 
Fail 
Checksum on control panel 
parameters failed. Contact security 
company to verify control panel 
program. 
18 Alarm 
Exit 
Error 
Detection device faulted at end of 
exit delay. 
41 CheckSum 
Fail, SDI 
Checksum on SDI device 
parameters failed. Contact security 
company.