Bosch 9 6 BLCC110U User Manual

Page of 32
Solution 64
18
Bosch Security Systems   09/06   BLCC110U
User Guide
Inputs > Input Testing >
Walk Test All Zones
MENU  3-9-0
This menu allows you to test all zones within an area at the same 
time.  To successfully walk test each zone, you must open and 
close each zone.
Enter programming mode (PIN + MENU) then,
1.  Press [MENU] + [3] + [9] + [0].
 
The keypad will display a list of areas that are available to 
walk test zones.
2.  Use the [
] and [] keys to select the area that you want to 
do walk test, then press [OK] to select.  Alternatively, you 
can enter the area number, then press [OK].
 
The keypad will scroll all zones that you can test.
To test Z001
open then close
Zone 1 Name
 
Press OK or MENU
To test Z002
open then close
Zone 2 Name
 
Press OK or MENU
3.  Open and close each zone that needs to be tested.  A 
zone that has been successfully tested will no longer 
scroll on the keypad display.
 
When all zones have been tested, the keypad will display:
Selected zones have been
Tested OK
Press OK or MENU
4.  Press [OK] to save and exit, or press [MENU] to exit 
without saving. 
Inputs > Input Testing >
Walk Test A Single Zone
MENU  3-9-1
This menu allows you to select a single zone to be tested via walk 
test.
Enter programming mode (PIN + MENU) then,
1.  Press [MENU] + [3] + [9] + [1].
 
The keypad will display a list of zones that are available to 
be tested via walk test.
2.  Use the [
] and [] keys to select the zone that you want 
to walk test, then press [OK] to select.  Alternatively, you 
can enter the zone number, then press [OK].
 
The keypad will display the zone to be tested.
To test Z001
open then close
Zone 1 Name
 
Press OK or MENU
3.  Open and close the zone that needs to be tested. 
 
When the zone has been successfully faulted and 
restored, the keypad will display:
Z001 Zone 1 Name
Test Successful
Press OK or MENU
4.  Press [OK] to save and exit, or press [MENU] to exit 
without saving. 
Outputs
The Solution 64 control panel has up to a maximum of 8 outputs.  
4 outputs are available as standard with an additional 4 available 
when  the  optional  output  expander  is  fitted.  Your  installer 
will advise you on the exact makeup and configuration of you 
system.
Outputs > Commands >
Output Status
MENU  4-0-0
This menu allows you to view the status of each output.
Enter programming mode (PIN + MENU) then,
1.  Ensure that the system is turned off.
2.  Press [MENU] + [4] + [0] + [0].
 
The keypad will display a list of outputs that the status 
may be viewed.
3.  Using the [
] and [] keys, highlight the output that you 
want to view the status information, then press [OK] to 
select.  Alternatively, you can enter the output number 
and then press [OK].
 
The keypad will display the following when the output is 
off and OK: