Gas-Fired Products 100 User Manual

Page of 53
 
 Form 
#43343530 
 
–4– 
JJuly 08
 
4.0) 
MINIMUM CLEARANCES TO COMBUSTIBLES 
 
Failure to do so may result in death, serious injury or
property damage.
Combustible material must be located outside the
clearance dimensions listed.
 
Minimum clearances to combustibles shall be measured from the outer surfaces as shown in the following diagram: 
 
 
 
 
 
 
 
MINIMUM CLEARANCES TO COMBUSTIBLES 
Mounted Horizontally 
Angle Mounted at 
45º 
Model No. 
Sides Ceiling* 
Below 
Ends 
45º Front  45º Rear 
PTS/PTU 40/25 
27”  6”  40” 30” 48” 12” 
PTS/PTU 50/30 
27”  6”  40” 30” 48” 12” 
PTS/PTU 75/50 
27”  6”  60” 
 30” 48” 12” 
PTS/PTU 100/65 
66” 
6” 
  88” ** 
40” 66” 20” 
PTS/PTU 125/80 
66” 6” 
101” 
** 
40” 66” 20” 
PTS/PTU 150/100 
84” 6” 
106” 
** 
48” 84” 24” 
PTS/PTU 175/110 
84” 6” 
106” 
** 
48” 84” 24” 
PTS/PTU 200/125 
84” 6” 
106” 
** 
48” 84” 24” 
 
* When used indirect vented, minimum clearance for CEILING must be:  12” for PTS/PTU 50-75 and 18” for 
PTS/PTU 100-200.  If optional corner and u-bend reflectors are not used, the clearance must be 18”. 
 
 ** Maximum clearance below reduces to 72” once you are 20ft. downstream from the control box. 
 
WARNING:  Certain materials or objects, when stored under the heater, will be subjected to radiant heat and 
could be seriously damaged.  Observe the Minimum Clearances to Combustibles listed in the manual and on the 
heater at all times. 
 
NOTE:  The clearances specified above must be maintained to combustibles and other materials that may be 
damaged by temperatures 90ºF above ambient temperature.  Clearances to combustibles are posted on the 
control box.  In areas used for storage of combustible materials where they may be stacked below the heater, 
NFPA54 requires that the installer must post signs that will “specify the maximum permissible stacking height to 
maintain the required clearances from the heater to combustibles.”  Space-Ray recommends posting these signs 
adjacent to the heater thermostat or other suitable  location that will provide enhanced visibility. 