Heat Mode 
 
When a call for heat (“W”) is received from the thermostat, if the “Cool” mode is not already active, the 
“T-T” terminal is energized and the blower on delay is started. The on-off pattern of DIP switch SW2 
(positions 1 and 2) select one of four blower on delay values (see Table 11). When the delay time has 
elapsed, the “HEAT” blower speed is energized.  The control remains in steady heat mode until the 
thermostat is satisfied. When the call for heat signal is removed, the “T-T” terminal is de-energized and 
the blower off delay is started. The on-off pattern of DIP switch SW2 (positions 3 and 4) select one of 
four blower off delay values (see Table 11). When the delay time has elapsed, the “HEAT” blower 
speed terminal is de-energized.
 
 
 
DIP SWITCH 2 SECTION STATE 
 
BLOWER DELAY TIMES 
Counter Flow 
ON - SEC 
ON - SEC 
OFF - MIN 
OFF 
OFF 
 
 
15 
30 
 
ON 
OFF 
 
 
24 
60 
 
OFF 
ON 
 
 
36 
120 
 
ON 
ON 
 
 
48 
240 
 
 
 
OFF 
OFF 
 
 
 
 
ON 
OFF 
 
 
 
 
OFF 
ON 
 
 
 
 
ON 
ON 
 
 
 
Table 11: ON and OFF Blower Delay Time Switch Settings
 
 
Motor Blower Speed 
 
 
 
Three interconnected blower speed outputs are provided. A “G” call for fan will provide power to the 
LOW speed tap only. A “W” heat call will provide power to the Heat speed tap only. A “Y” cooling call 
will provide power to the Cool speed tap only. 
 
In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by 
the input that was first initiated. In the case where the control is in a cooling mode with both “Y” and 
“W” inputs energized and then the “Y” input is removed, the cooling blower off time will be executed 
prior to the control switching into a heating mode. In the case where the control is in a heating mode 
with both “Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time 
will be executed prior to the control switching into a cooling mode. In the case where a call for fan “G” 
already exists and either a “W” or a “Y” call is initiated, the blower speed will switch to the respective 
“W” or a “Y” speed following the blower on delay for that call.
 
 
The speed taps are interconnected and interlocked, only one speed may be powered at any one time. 
When a speed is to be operated, the speed select relays are operated to select the path to the motor 
tap and then the enable relay is operated to switch the operating power to the selected motor speed 
tap. If the speed of the running motor is to be changed, first the enable relay removes power from the 
motor, the new speed is selected and then power is restored to the motor. 
 
 
 
Blower On and Off Delays 
 
Four  Heat blower on and four blower off delays are selected by two dip switches for each function. 
Refer to Table 11 for specific delay values.