INSTALLATION
14)
 Re-install pilot shield.
15) 
Set aeration on both front and rear burner 
for LP gas;
 
  Rear 
 
3/16"
 
  Front 
3/8"
16)
 Reverse steps 8 to 4.
17)
 Remove the Power Module by lifting it up off 
of the velcro and move it over to the side.
Power Module
Control Module
18)
  Remove the Control Module, located behind 
the power module, by lifting it up off of the 
velcro.
19)
 Remove the J9 jumper using needle nose 
pliers, located under the heat shield.
20)
 Reverse steps 18 to 17. Be careful not to 
pinch wires.
21)
 Remove the 2 wires connected to the
 modulating 
coil. 
Modulating Coil
22) 
Using a Torx T20, or slotted screwdriver, 
remove and discard the three pressure 
regulator mounting screws and rubber 
diaphram.
23)
 Insure that the new rubber gasket is 
properly positioned and install the new 
modulating pressure regulator assembly 
to the valve using the screws supplied 
with the kit. Tighten screws securely.
24) 
Reattach 2 wires to modulating coil.
25)
 Install the enclosed identifi cation label 
to the valve body where it can be easily 
seen. The label is found in the coil pack-
age.
26)
 Attach the LP conversion decal near or 
on top of the serial # decal located on a 
metal plate under the unit. 
27) 
Replace the yellow "Natural Gas" label 
with the red "Propane" label on the valve 
assembly.
28)  
Ensure proper installation of venting is 
complete, gas line is connected and then 
turn on power to unit.
29) 
Check for gas leaks.
30)
 Check inlet (12" wc) and outlet (10" wc) 
pressures.
31)
 Check operation of fl ame control using 
the manual control box located on the 
right side under the fi rebox.
32)
 Re-install logs and fl ush door. Check for 
proper fl ame appearance and glow on 
logs. 
WARNING!
This conversion kit should be installed 
by a qualifi ed service agency in ac-
cordance with the authority having 
jurisdiction. If the information in these 
instructions are not followed exactly, a 
fi re, explosion or production of carbon 
monoxide may result causing property 
damage, personal injury or loss of life. 
The qualifi ed service agency is respon-
sible for the proper installation of this 
kit. The installation is not proper and 
complete until the operation of the con-
verted appliance is checked as speci-
fi ed in the manufacturer's instructions 
supplied with the kit.
Installer Notice:
These instructions must be left 
with the appliance.
J9 Jumper