 L676E Direct Vent Gas Fireplace
15
INST
ALLA
TION
VENTING ARRANGEMENTS 
HORIZONTAL TERMINATION (FLEX)
Regency
®
 Direct  Vent System 
These venting systems, in combination with the L676E, have been tested and listed as a direct vent heater system by Intertek. The location of the 
termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the 
parts needed to install the L676E using a fl exible vent.
Notes: 
1)  Liner sections should be continuous 
without any joints or seams.
2)  Only Flex pipe purchased from FPI may 
be used for Flex installations.
3)  Horizontal vent must be supported every 
3 feet.
4)  A wall thimble is mandatory for all 
horizontal terminations due to high 
temperatures.
INSTALLATION
 
FPI Kit # 
Length 
Contains:
#946-618
6 Feet
1) 
8” fl exible liner (Kit length)
2) 
5” fl exible liner (Kit length)
3) spring 
spacers 
(3)
4) thimble 
(2)
5) 
AstroCap termination cap (1)
6) screws 
(12)
7) 
tube of Mill Pac (1)
8) plated 
screws 
(8)
9) 
S.S. screws #8 x 1-1/2” drill point, (4)
10)  vinyl siding standoff
#946-616
10 Feet
 
* A Vent Guard is required when the AstroCap 
is installed above grade at 7 feet or lower.