INSTALLATION
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual  shut-off  valve  during  any  pressure
testing of the gas supply piping system at test
pressures  equal  to  or  less  than  3.45  kPa.
Disconnect piping from valve at pressures over
3.45 kPa.
The manifold pressure is controlled by a regu-
lator built into the gas control, and should be
checked at the pressure test point.
Note:  To  properly  check  gas  pressure,
both  inlet  and  manifold  pressures
should be checked using the valve
pressure  ports  on  the  valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen  the  "IN"  and/or  "OUT"  pressure
tap(s),  turning  counterclockwise  with  a
1/8"  wide  flat  screwdriver.
3) Attach  manometer  to  "IN"  and/or  "OUT"
pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON"
position.
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
6) When finished reading manometer, turn off
the  gas  valve,  disconnect  the  hose  and
tighten  the  screw  (clockwise)  with  a  1/8"
flat screwdriver.  Note:  Screw  should  be
snug,  but  do  not  over  tighten.
S.I.T. VALVE DESCRIPTION
1) Gas cock knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection
Point
Important:  Always  check  for  gas  leaks
with  a  soap  and  water  solution  or  gas
leak  detector.  Do  not  use  open  flame  for
leak  testing.
P121/P121LC/P121RC/P131-NG
System Data
For 0 to 4500 feet altitude
Burner  Inlet  Orifice  Sizes: #31
Pilot Orifice NG
Max.  Input  Rating 42 mj.
Min.  Input  Rating 22 mj.
Supply  Pressure min. 1.13 kPa
Manifold  Pressure
(High)
1.00 kPa
Log Set: Ceramic fibre, 8 per set.
Flue  System:  Regency  Astrocap
TM
,  Re-
gency Direct Vent System (Flex) and  Simp-
son Dura-Vent Direct Flue System
GAS LINE
INSTALLATION
The gas line can be brought through either the
right, the left side  or the bottom of the appliance.
The gas valve is situated on the bottom of the
unit.
The gas line connection may be made of rigid
pipe, copper pipe or an approved flex connec-
tor. (If you are using rigid pipe, ensure that the
valve  can  be  removed  for  servicing.)  Since
some municipalities have additional local codes
it  is  always  best  to  consult  with  your  local
authorities  and  AS5601-2004  (Australian
Installation  Code)  NZS  5261(New  Zealand
Installation Standard).
When  using  copper  or  flex  connectors  use
only approved fittings. Always provide a union
so that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and flex
connectors are usually considered to meet this
requirement.
Periodically  check  the  pilot  flames.  Cor-
rect  flame  pattern  has  three  strong  blue
flames:  1  flowing  around  the  thermopile,
1 around the thermocouple  and  1  flowing
across  the  burner  (it  does  not  have  to  be
touching  the  burner).
Note: If  you  have  an  incorrect  flame  pat-
tern,  contact  your  Regency  dealer
for  further  instructions.
Incorrect  flame  pattern  will  have  small,
probably  yellow  flames,  not  coming  into
proper  contact  with  the  rear  burner  or
thermopile  or  thermocouple.
P121/P121LC/P121RC/P131-LPG
System Data
For 0 to 4500 feet altitude
Burner  Inlet  Orifice  Sizes: #50
Pilot  Orifice  LPG
Max.  Input  Rating 41 mj.
Min.  Input  Rating 22 mj.
Supply  Pressure min. 3.00 kPa
Manifold  Pressure
(High)
2.65 kPa
Log Set: Ceramic fibre, 8 per set.
Flue  System:  Regency  Astrocap
TM
,  Re-
gency Direct Vent System (Flex) and  Simp-
son Dura-Vent Direct Flue System
PILOT  ADJUSTMENT