VENTING ARRANGEMENTS 
ALLOWABLE VERTICAL TERMINATIONS
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90
o
 elbows,  with 
Rigid Pipe Venting Systems for Propane and Natural Gas.  Two  45
o  
elbows equal to one 90
o
 elbow.  Maximum of four 45
o
 elbows allowed.
•   Vent must be supported at offsets.
•   Firestops are required at each fl oor level and whenever passing through a wall.
•   Maintain clearances to combustibles as listed in the "Clearances" section.
• 
Refer to "Vent Restrictor Position" section for details on how to change the vent restrictor to Set 1, Set 2 or Set 3 if required.
Note:  Must use optional fl ue adapter when using Rigid Pipe (Part # 770-994).