Regency P40 User Manual

Page of 48
Regency
®
 P40 Direct Vent Gas Fireplace
19
INST
ALLA
TION
V
H1
H
V1
V1
V
H
Vertical Venting with Two (2) 90
o
 Elbows
Vertical Venting with Three (3) 90
o
 Elbows
One 90
o
 elbow = Two 45
o
 elbows.
One 90
o
 elbow = Two 45
o
 elbows.
 
Option  V 
    H 
V + V1 
 
     A) 
0' Min.  2' Max.  1' Min. 
 
     B) 
1' Min.  4' Max.  2' Min. 
 
     C) 
2' Min.  5' Max.  3' Min. 
 
     D) 
3' Min.  6' Max.  4' Min. 
 
     E) 
4' Min.  7' Max.  5' Min. 
 
     F) 
5' Min.  8' Max.  6' Min.
With these options, max. total 
pipe length is 30 feet with min. 
of 6 feet total vertical and max. 
8 feet total horizontal.
Please note min. 1 foot 
between 90
o
 elbows is 
required.
For additional vertical venting with 2 
x 90
o
 elbows, refer to next page.
 
Option        V 
H + H1  V + V1
 
     A) 
0' Min.  2' Max.  3' Min.
 
     B) 
1' Min.  2' Max.  3' Min.
 
     C) 
2' Min.  3' Max.  4' Min.
 
     D) 
3' Min.  4' Max.  6' Min.
 
     E) 
4' Min.  5' Max.  7' Min.
 
     F) 
5' Min.  6' Max.  8' Min.
 
     G) 
6' Min.  7' Max.   9' Min.
  
     H) 
7' Min.  8' Max.  10' Min. 
With these options, max. 
total pipe length is 30 feet 
with min. of 10 feet total 
vertical and max. 8 feet 
total horizontal.
Please note min. 1 foot 
between 90
o
 elbows is 
required.
INSTALLATION
VENT RESTRICTOR SETTING:
When total vertical exceeds total horizontal by 2x the vent restrictor 
setting is set to 1.
VENT RESTRICTOR SETTING:
When total vertical exceeds total horizontal by 3x the vent 
restrictor setting is set to 1.