Vent Information 
A.  Venting Termination Minimum Requirements
NOTICE:
Termination must exhaust above air inlet elevation.  
•  It is recommended that at least 60 inches (1.52m) of vertical 
pipe be installed when appliance is vented directly through a 
wall.  This will create a natural draft, which will help prevent 
the possibility of smoke or odor venting into the home during 
a power outage. 
•  It will also keep exhaust from causing a nuisance or hazard 
by exposing people or shrubs to high temperatures.  
•  The safest and preferred venting method is to extend the 
vent vertically through the roof or above the roof.
J or K
X
V
M
I
H
A
V
G
B
V
V
A
B
V
F
V
C
B
B
E
L
V
D
V
Electrical
Service
V
N
V
N
V
N
N
V
Inside Corner
FIXED 
CLOSED
OPEN
OPEN
FIXED 
CLOSED
V
X
G
G
Termination Cap
Air Supply Inlet
Gas Meter
Restricted Area
O
P
Figure 37.1
A
12 in.
Above Finish Grade (the grade surface 
must be a non-combustible material
B
12 in.
Open door or window: below or to the side
B
12 in.
Open door or window: above
C
6 in.
Permanently closed window: above, below 
or to the side
D
18 in.
Vertical clearance to a ventilated soffi t 
located above the terminal within a hori-
zontal distance of 2 ft from the center-line 
of the terminal 
E
12 in.
Clearance to unventilated soffi t
F
12 in.
Clearance to outside corner
G
12 in.
Clearance to inside corner
H
36 in.
Above gas meter/regulator measured from 
horizontal center-line of regulator
I
36 in. USA
72 in. Canada
Clearance to service regulator vent outlet
J
12 in.
Clearance to non-mechanical air supply 
inlet to the building or the combustion air 
inlet to any other appliance
K
10 ft horizontal
3 ft vertical
Clearance to mechanical air supply
L
7 ft.
Above paved sidewalk, paved driveway 
located on public property
M
12 in.
Under an open veranda, porch, deck or 
balcony
N
See Note 
below*
Electric service: above, below or to the 
side (location must not obstruct or interfere 
with access)
O
24 in.
Adjacent building, fences and protruding 
parts of the structure
P
12 in.
Clearance above roof line for vertical 
terminations
An Outside Air Kit is required on all installations.
   Outside Air Kit must be ordered separately.
24 in.
Above grass, top of plants, wood or any other com-
bustible
12 in.
Clearance from any forced air intake of other appli-
ance
12 in.
Clearance horizontally from combustible wall
15 in.
Vented directly through a wall, minimum length of 
horizontal pipe
12 in. horizontal
12 in. vertical
Minimum horizontal or vertical terminations must 
protrude from wall
*NOTE:  Consult local building, fi re offi cials or authorities having 
jurisdiction.  Local codes or regulations may require different 
clearances.
NOTICE:
Do NOT Terminate Vent:
•  In any location that will allow fl ue gases or soot to enter 
or stain the building.
  In any location which could create a nuisance or hazard.
•  In any enclosed or semi-enclosed area such as a carport, 
garage, attic, crawl space, under a sun deck or porch, 
narrow walkway. 
•  Closely fenced area, or any location that can build up 
a concentration of fumes such as a stairwell, covered 
breezeway, etc.