Emerson AE8-1385 User Manual

Page of 12
7
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
B
U
L
L
E
T
I
N
ALERT
TRIP / LOCK
POWER
      
    
    1       Long Run Time
    2       Compressor (Pressure) Trip
    3       Pressure Switch Cycling
    4       Locked Rotor
    5       Compressor (Mod Run) Trip
    6       Open Start Circuit
    7       Open Run Circuit
    8       Welded Contactor
    9       Low Voltage
          
DC SOL operating range: 18-28VDC
Compressor second stage is
energized when Y & Y2 are 24VAC
          
PROT breaks 24VAC common
leg of compressor contactor coil
Reset codes and PROT lockout
by removing 24VAC to module
Flash      Event
Two Stage Control
Active Protection
C
S
R
47
37
62
112
67
Figure 2 – Module Dimensions in Millimeters
Y2
Y
Data Port
L
R
C
PROT
Solenoid
For Use With
Copeland Scroll
UltraTech
Compressors
P/N: 543-XXXX-XX
065312345
Patent: 6,615,594
Use With Class 2
Circuits Only
Supply 24VAC
            50/60Hz
Power 1.5VA
Figure 3 – Terminal Locations