Alert Code
Alert Condition
Lockout Level
Lockout 
Indication
Normal Run
Solid Green
Normal operation, no trip.
N/A 
N/A 
Code1 
Yellow Flash 1
Long run time. Compressor is running for more than 
18 hours at full load. (Code1 is disabled in Heat Pump 
mode.)
N/A N/A 
Code2 
Yellow Flash 2
Compressor Pressure trip. Compressor runs for 12sec 
to 15min followed by a compressor trip condition lasting 
longer than 7min.
4x consecutive, 
10x total 
Red: Flash 2 
Code 3 
Yellow Flash 3
Pressure switch cycling. Compressor runs for 12sec to 
15min followed by a compressor trip lasting between 
35sec to 7min. 
4x consecutive, 
10 total
Red: Flash 3
Code4 
Yellow Flash 4
Locked rotor. Compressor trips within a compressor run 
time of 12sec and does not start within 35sec.
10x consecutive  Red: Flash 4
Code5 
Yellow Flash 5
Compressor moderate run trip. Compressor runs for 
15min to 18hrs followed by a compressor trip lasting 
longer than 7min. 
4x consecutive, 
10x total
Red: Flash 5
Code6 
Red Flash 6
Open start circuit. Module has detected Y or Y1, and 
current in the R winding of the compressor and no 
current in the S winding of the compressor for 2 seconds. 
1 occurrence
Red: Flash 6
Code7 
Red Flash 7
Open run circuit. Module has detected Y or Y1, and 
current in the S winding of the compressor and no current 
in the R winding of the compressor for 2 seconds. 
1 occurrence
Red: Flash 7
Code8 
Yellow Flash 8
Welded Contactor. Module has detected line currents 
in R and S windings, and Y or Y1 is at 0 VAC for 15 
seconds.
N/A N/A 
Code9 
Yellow Flash 9
Low Voltage. Module has detected a 24 VAC supply 
voltage below 17 VAC +/- 1 VAC for 2 seconds
N/A N/A
Code10 
Red Flash 10
Over Current Protection. PROT terminal has above a 2A 
input for more than 40 milliseconds.
1 occurrence
Red: Flash 10
Table 1 – Flash Code Description