Drain Connection 
and Location
NOTICE
Figure 11
Indoor Return Air Grille Installation
Return Air Grille Options
Figure 12
Option 2 
Field Supplied
Return Air Grille
Option 1 
VPRG4 Return Air Grille
with Access Panel
There are  two Indoor Return Air Grille options as shown in 
Figure  12.  Choose  the  option  that  best  suits  your  needs. 
Use the installation instructions provided with accessories 
for installation details. 
NOTE: All Vert-I-Pak chassis are shipped with a 20” x 
14” filter installed. If an accessory filter holder is to be 
used, you MUST remove the factory shipped filter from 
the chassis. Do NOT use two filters.
A field-supplied (25” x 20”) filter is 
mounted inside the hinged access 
door.
Kit  contains  hinge  bracket  for 
mounting the door with the return 
air  openings  high  or  low  on  the 
door  for  optimal  sound  attenua-
tion.
It  is  recommended  to  install  the 
door  with  the  hinge  on  the  right 
side  and  the  return  air  openings 
high on the door.
Must have a minimum of 250
square inches of free area.
There  are  the  Friedrich  recommended  return  air 
grille/filter/access  panel  arrangements.  Consult 
Friedrich on other arrangements. Improper return air 
arrangements will cause performance problems.
Return  air  arrangements  are  shown  from  the  front, 
but can also be installed from the right or left side of 
the unit.
NOTES:
1) 
The unit basepan has three (3) provisions (left, right, 
and rear) for connecting an external condensate drain.
2)    The supplied drain kit must be connected to one of the 
three (left, right, or rear) ¾” FPT connections on the 
unit basepan. Use of rear fitting without connection to 
DWV  system  (drain,  waste,  vent)  may  result  in 
staining of the outside wall. 
3) 
Insert  the  provided  ¾”  nipple  into  the  determined 
connection using field supplied teflon tape or pipe joint
compound.
4) 
With  the  threaded  end  of  the  supplied  ¾”  union, 
connect to the nipple with  teflon tape or pipe joint 
compound. 
5) 
Hand-tighten  all  fittings  to  prevent  damage  to  unit  or 
fittings. 
6) 
A field supplied drain system must now be installed to 
the slip end of the union. A trap is recommended and 
drain  connections  should    be  connected  to  building 
DWV system. 
7) 
Pitch the drain line on a ¼” downward slope for every 
foot (1’) of lateral horizontal run  to the DWV. 
8) 
The remaining two connections must be plugged using 
the  two  ¾”  pipe  plugs  (provided)  and  field  supplied 
teflon  tape  or  pipe  join  compound.  Hand-tighten  to 
prevent damage to unit or fittings.
9) 
Do not thread metal or copper pipe fittings directly into 
unit. 
10)  Check system for leaks. 
11)  Failure  to  follow  these  procedures  may  result  in 
serious property damage.  
12)  A  field  supplied  secondary  condensate  pan  may  be 
required. Check with local codes. 
Ductwork
The supply duct system should be designed via a recognized 
method such as the equal friction method, or velocity reduction 
method, using the appropriate duct calculator(s) for the type(s) 
of duct (i.e. metal duct, duct board, or flex duct) being used in 
the  system.    The  duct  system  should  be  designed  for  a 
maximum friction rate of .30" water column taking into conside-
ration all fittings, registers and/or diffusers.  DO NOT operate 
unit without a supply duct attached.  
The  return  air  to  Vert-I-Pak  "A"  series  units  MUST  NOT  be 
ducted, and all units MUST have a free return air configuration 
to perform properly.