Chassis Installation/
Installed View
Correct CFM (if needed):  
Chart B – Correction Multipli
ers
Chassis Installation
Install the following components
A.  Ensure that the wall plenum is installed in accordance 
with the instructions listed on Pages 6-10.
B.  Place the chassis into the closet with the outdoor side 
facing the wall plenum opening.
C.  Slide the chassis into the wall plenum until the plenum 
divider seal is established. (See Figure 13)
Determining the Indoor CFM:  Chart A – CFM
Model
VEA12/VHA12
VEA18/VHA18
VEA09/VHA09
ESP (")
.00"
.10"
.20"
.30”
Low
340
300
230
140
High
385
340
280
190
Low
420
350 *
290
250
High
470
420 **
350
300
Low
430
400
340
290
High
480
450
400
330
 
Highlighted values indicate rated performance point.
 
Rated performance for VEA12 

 
Rated Performance for VHA12
** 
Indoor Air Flow Data
Indoor air flow may be determined by measuring the exter-
nal  static  pressure  (ESP)  of  the  duct  system  using  an 
inclined manometer or magnehelic gauge, then consulting 
chart  “A”  to  determine  actual  air  flow.    Rated  air  flow  for 
each  unit  is  obtained  at  .10”  W.C.  when  operating  with  a 
clean  filter  and  a  dry  coil  (i.e.  heating)  on  the  indicated 
speed at 230 Volts.  Use the air flow correction multipliers 
contained in chart “B” to determine accurate air flow under 
the listed conditions.  Under no circumstances should the 
Vert-I-Pak  equipment  be  operated  at  an  external  static 
pressure in excess of .30” W.C.  Operation of the Vert-I-Pak 
under  these  conditions  will  result  in  inadequate  air  flow 
leading to poor performance and/or premature component 
failure.
For LOW speed operation, connect the fan output terminal 
from  the  thermostat  to  the  GL  terminal  of  the  electronic 
control.  For HIGH speed operation, connect the fan output 
terminal  from  the  thermostat  to  the  GH  terminal  of  the 
electronic  control.    For  thermostats  with  two-speed  fan 
capabilities,  connect  the  LOW  speed  output  to  the  GL 
terminal, and the HIGH speed output to the GH terminal.
Moving parts hazard
Turn off electric power before servicing 
this component.
Fan can start automatically.
Failure  to  do  so  can  result  in  property 
damage, personal Injury and/or death.
Cut/Sever Hazard
     
CAUTION
Some edges may be sharp, use gloves 
or other hand protection when handling 
unit.  
Failure  to  do  so  can  result  in  minor  to 
moderate personal injury.
The Vert-I-Pak chassis must be inserted into the wall 
plenum  so  that  the  plenum  divider  gasket  makes 
contact with the plastic condenser baffle on the unit. 
The  chassis  will  fit  approximately  2  ⅜"  into  the  wall 
plenum. 
Excessive Weight Hazard
Use two or more people when installing 
your air conditioner.
Failure to so can resut in back or other 
injury.
     