CAUTION
See the manual shipped with the roof curb for assembly and
installation instructions.
CLEARANCES
36”; minimum
roof overhang
UNIT CLEARANCES
Adequate clearance around the unit should be kept for safety,
service, maintenance, and proper unit operation.  A total clear-
ance of 75” on the main control panel side of the unit is rec-
ommended to facilitate possible fan shaft, coil, electric heat
and gas furnace removal.  A clearance of 48” is recommended
on all other sides of the unit to facilitate possible compressor
removal, to allow service access and to insure proper venti-
lation and condenser airflow.  The unit must not be installed
beneath any obstruction.  The unit should be installed re-
mote from all building exhausts to inhibit ingestion of exhaust
air into the unit fresh air intake.
Insulated
Panels
Roof Curb Installation
ROOF CURB POST-INSTALLATION
CHECKS
After installation, check the top of the curb, duct connection
frame and duct flanges to make sure gasket has been ap-
plied properly.  Gasket should be firmly applied to the top of
the curb perimeter, duct flanges and any exposed duct con-
nection frame.  If gasket is loose, re-apply using strong
weather resistant adhesive.
P
ROTRUSION
Inspect curb to ensure that none of the utility services (elec-
tric) routed through the curb protrude above the curb.
I
F
 
PROTRUSIONS
 
EXIST
DO
 
NO
 
ATTEMPT
 
TO
 
SET
 
UNIT
 
ON
 
CURB
.
CAUTION
ROOF TOP DUCT CONNECTIONS
Install all duct connections on the unit before placing the unit
on rooftop.