Goodman Mfg IO-367B User Manual

Page of 20
8
CPC Weights
(lbs)
CPC Weights
(lbs)
15 Tons
20 Tons
Corner Weight - A
580
655
Corner Weight - B
540
535
Corner Weight - C
475
510
Corner Weight - D
440
420
Unit Shipping Weight
2150
2235
Unit Operating Weight
2035
2120
X (Inches)
60"
58"
Y (Inches)
43"
40"
DATA
NOTE: These weights are without accessories installed.
T
O
 
PREVENT
 
SEVERE
 
DAMAGE
 
TO
 
THE
 
BOTTOM
 
OF
 
THE
 
UNIT
DO
 
NOT
 
FORK
 
LIFT
 
UNIT
 
AFTER
 
WOOD
 
STRUTS
 
HAVE
 
BEEN
 
REMOVED
.
CAUTION
Bring condenser end of unit into alignment with the curb.  With
condenser end of the unit resting on curb member and using
curb as a fulcrum, lower opposite end of the unit until entire
unit is seated on the curb.  When a rectangular cantilever
curb is used, care should be taken to center the unit.  Check
for proper alignment and orientation of supply and return
openings with duct.
R
IGGING
 R
EMOVAL
T
O
 
PREVENT
 
DAMAGE
 
TO
 
THE
 
UNIT
DO
 
NOT
 
ALLOW
 
CRANE
 
HOOKS
 
AND
 
SPREADER
 
BARS
 
TO
 
REST
 
ON
 
THE
 
ROOF
 
OF
 
THE
 
UNIT
.
CAUTION
Remove spreader bars, lifting cables and other rigging equip-
ment.
ELECTRICAL WIRING
HIGH VOLTAGE! 
D
ISCONNECT
 
ALL
 
POWER
 
BEFORE
 
SERVICING
 
OR
 
INSTALLING
 
THIS
 
UNIT
. M
ULTIPLE
 
POWER
 
SOURCES
 
MAY
 
BE
 
PRESENT
. F
AILURE
 
TO
 
DO
 
SO
 
MAY
 
CAUSE
 
PROPERTY
 
DAMAGE
PERSONAL
 
INJURY
 
OR
 
DEATH
.
WARNING
HIGH VOLTAGE! 
T
O
 
AVOID
 
PERSONAL
 
INJURY
 
OR
 
DEATH
 
DUE
 
TO
 
ELECTRICAL
 
SHOCK
DO
 
NOT
 
TAMPER
 
WITH
 
FACTORY
 
WIRING
. T
HE
 
INTERNAL
 
POWER
 
AND
 
CONTROL
 
WIRING
 
OF
 
THESE
 
UNITS
 
ARE
 
FACTORY
-
INSTALLED
 
AND
 
HAVE
 
BEEN
 
THOROUGHLY
 
TESTED
 
PRIOR
 
TO
 
SHIPMENT
C
ONTACT
 
YOUR
 
LOCAL
 
REPRESENTATIVE
 
IF
 
ASSISTANCE
 
IS
 
REQUIRED
.
WARNING
T
O
 
PREVENT
 
DAMAGE
 
TO
 
THE
 
WIRING
PROTECT
 
WIRING
 
FROM
 
SHARP
 
EDGES
. F
OLLOW
 
NATIONAL
 
ELECTRICAL
 
CODE
 
AND
 
ALL
 
LOCAL
 
CODES
 
AND
 
ORDINANCES
. D
O
 
NOT
 
ROUTE
 
WIRES
 
THROUGH
 
REMOVABLE
 
ACCESS
 
PANELS
.
CAUTION
C
ONDUIT
 
AND
 
FITTINGS
 
MUST
 
BE
 
WEATHER
-
TIGHT
 
TO
 
PREVENT
 
WATER
 
ENTRY
 
INTO
 
THE
 
BUILDING
.
CAUTION
For unit protection, use a fuse or HACR circuit breaker that is
in excess of the circuit ampacity, but less than or equal to the
maximum overcurrent protection device. DO NOT EXCEED
THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN
ON UNIT DATA PLATE.
All line voltage connections must be made through weather-
proof fittings.  All exterior power supply and ground wiring
must be in approved weatherproof conduit.
The main power supply wiring to the unit and low voltage
wiring to accessory controls must be done in accordance with
these instructions, the latest edition of the National Electrical
Code (ANSI/NFPA 70), and all local codes and ordinances.
All field wiring shall conform with the temperature limitations
for Type T wire (63°F/35°C rise).
The main power supply shall be three-phase, three wire.  The
unit is factory wired for the voltage shown on the unit’s data
plate.
NOTE: If supply voltage is 208V, all leads on primary of trans-
former TRANS1 must be moved from the 230V to the 208V
tap.
Main power wiring should be sized for the minimum wire
ampacity shown on the unit’s data plate.  Size wires in accor-
dance with the ampacity tables in Article 310 of the National
Electrical Code.  If long wires are required, it may be neces-
sary to increase the wire size to prevent excessive voltage
drop.  Wires should be sized for a maximum of 3% voltage
drop.