PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of inter-
connecting 
line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for 
evaporator + adder for line set.
F2RP/F2FP040 
0  –
F2FP048 
F2FP060 
0* 
F2FV060 
G4FA030S14T2A 0 
G4FA030S14T2B –
G4FA036S14T2A 
0 0 0 –
G4FA036S17T2A 0 
G4FA036S21T2A 0 
G4FA036S21T2B –
G4FA048S17T2A 
G4FA048S17T2C –
G4FA048S21T2A 
G4FA048S21T2C 
G4FA060S21T2C 
G4FA060S24T2C 
G4FD024H14T2A 
G4FD024H14T2B 
G4FD024H17T2A 
G4FD024H17T2B 
G4FD030H17T2A 
G4FD035H14T2A 
G4FD036H17T2A 
0 0 0 –
G4FD036H21T2A 
G4FD042H21T2A 
G4FD042H21T2C 
G4FD046H17T2A 
G4FD046H17T2C 
G4FD048H21T2A 
G4FD048H21T2C 
G4FD048H24T2A 
G4FD048H24T2C 
G4FD060H24T2C 
G4FD061H24T2C 
F4FP024H06T2A 0 
F4FP024H06T2B –
F4FP030H06T2A –
F4FP036H06T2A 
F4FP040H06T2A –
F4FP042H06T2A 
F2FP048H06T2C 
F2FP060H06T2C 
0* 
F2FV060H06T2C 
FOOTNOTES:
1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
3. A TXV kit must be used with these coils to obtain system performance (2A, 2B, and 2C indicate 1TVM series).
* This loose coil match does not achieve 13 SEER.
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)
Outdoor Unit 
H2RD018S06 H2RD024S06 H2RD030S06 H2RD036S06 H2RD042S06 H2RD048S06 H2RD060S06
Required 
TXV
1TVM2A1 
1TVM2(A,B)1
1TVM2A1 1TVM2A1 1TVM2C1 1TVM2C1 1TVM2C1 
Factory R-22 Charge, lbs-oz
4 - 9 
6 - 3 
5 - 13 
6 - 0 
8 - 13 
8 - 6 
10 - 2 
Indoor Coil
1,2
TXV KIT
3
 - Additional Charge, Oz