Carrier 48SS024 User Manual

Page of 8
CERTIFIED DIMENSION PRINT
INDOOR COIL
OUTDOOR COIL
INDOOR COIL ACCESS
REQ’D CLEARANCES FOR SERVICING — in. (mm)
Duct Panel . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit Top . . . . . . . . . . . . . . . . . . . . . 36 (914.4)
Side Opposite Ducts . . . . . . . . . . . . . . 36 (914.4)
Compressor Access
. . . . . . . . . . . . . . 36 (914.4)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L
— in. (mm)
Maximum Extension of Overhangs . . . . . . 48 (1219.2)
Unit Top . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct Side of Unit
. . . . . . . . . . . . . . . . . 2 (50.8)
Side Opposite Ducts . . . . . . . . . . . . . . 14 (355.6)
Bottom of Unit
. . . . . . . . . . . . . . . . . . . . . . 0
Flue Panel
. . . . . . . . . . . . . . . . . . . 36 (914.4)
NEC (National Electrical Code) REQ’D CLEARANCES
— in. (mm)
Between Units, Control Box Side . . . . . . . 42 (1066.8)
Unit and Ungrounded Surfaces,
Control Box Side
. . . . . . . . . . . . . . . 36 (914.4)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side
. . . 42 (1066.8)
UNIT
48SS
ELECTRICAL
CHARACTERISTICS
UNIT
WEIGHT
CORNER WEIGHT
(lb/kg)
lb
kg
A
B
C
D
048080
208/230-1-60
414
188
107/49
83/38
158/72
66/30
048100/120/140
208/230-1-60
426
193
110/50
86/39
159/72
71/32
060080
208/230-1-60
453
206
117/53
93/42
167/76
76/35
060100/120/140
208/230-1-60
465
211
120/55
96/44
167/76
82/37
UNIT
48SS
CENTER OF GRAVITY
(in./mm)
X
Y
Z
048080
28.76/731
23.46/596
15.35/390
048100/120/140
28.42/722
23.42/595
15.35/390
060080
28.36/720
23.27/591
15.35/390
060100/120/140
27.95/710
23.23/590
15.35/390
NOTE: Clearances must be maintained to prevent recircu-
lation of air from outdoor fan discharge.
5