A.O. Smith 2600 User Manual

Page of 83
14
FLAME SENSOR
Each  burner  is  equipped  with  a  flame  sensor  to  detect  the 
presence of the burner flames at high and low fire conditions. If 
no flame is sensed, the gas valve will close automatically. The 
voltage sensed by the flame sensor will also be displayed on the 
Burner Screen.
FIGURE 10.  FLAME SENSOR
WATER TEMPERATURE LIMIT CONTROLS
The “XB/XW” models incorporate an outlet water sensor having 
dual sensors, that are factory set at 210°F (99°C).
MAIN POWER SUPPLY SWITCH
The main power supply switch is a padlockable switch. This switch 
pro vides 120V from the power supply to the boiler.
This switch needs to be turned off when servicing the boiler.
Note: The Enable/Disable Switch on the front of the boiler 
does not interrupt electrical power to the boiler.
FIGURE 11.  MAIN POWER SUPPLY SWITCH
WATER TEMPERATURE SENSORS
FIGURE 12.  WATER TEMPERATURE SENSORS
Temperature  sensors  are  threaded  immersion  probes. 
Temperature  probes  have  embedded  temperature  sensors 
(thermistors). The boiler’s control system monitors these sensors 
to determine water temperature at various points in the system. 
INLET AND OUTLET TEMPERATURE SENSORS
All  models  have  two  inlet  and  two  outlet  temperature  sensors 
for each heat exchanger, factory installed to monitor the water 
temperature entering and leaving the boiler. The Inlet Probe is 
a temperature sensor only and has two leads. The Outlet probe 
also  contains  the  manual  reset  high  temperature  limit  switch 
and  has  four  leads. The  control  system  displays  the  Inlet  and 
Outlet water temperatures sensed from these two sensors on the 
default Temperatures screen.
REMOTE SENSORS
All models are supplied from the factory with a remote sensor. 
The remote sensor is used to control system water temperature 
for a single boiler in a domestic hot water storage tank or in the 
return line from a primary/secondary hydronic heating system.
The  boiler  will  modulate  its  firing  rate  in  response  to  the 
actual  system  temperature  and  load  conditions.  The  control  
system displays the temperature sensed from the remote sensor  
as  the  “Lead  Lag”  temperature  on  the  default  Temperatures 
screen.
LOW WATER CUTOFF DEVICE (LWCO)
Low water cutoff device is normally a closed switch that opens 
when water drops below a preset level. Each model is equipped 
with a factory installed LWCO. LWCO board is connected to the 
electronic panel, whereas the sensor probe is connected to the 
heat exchanger.
FIGURE 13.  LWCO BOARD AND PROBE