A.O. Smith 2600 User Manual

Page of 83
16
CIRCULATING PUMP
A circulating pump is used when a system requires a circulating 
loop or there is a storage tank used in conjunction with the boiler.  
Install  in  accordance  with  the  current  edition  of  the  National 
Electrical  Code,  NFPA  70  or  the  Canadian  Electrical  Code, 
CSA  C22.1.  All  bronze  circulating  pumps  are  recommended 
for  use  with  commercial  boilers.  Some  circulating  pumps  are 
manufactured  with  sealed  bearings  and  do  not  require  further 
lubrication. Some circulating pumps must be periodically oiled. 
Refer  to  the  pump  manufacturer’s  instructions  for  lubrication 
requirements.
XB HYDRONIC BOILERS: The circulating pump is not provided 
on standard models (optional) and must be obtained and installed 
in the field.
XW HOT WATER BOILERS: The circulating pump is integral to 
the XW models. This pump has been lubricated at the factory, 
and  future  lubrication  should  be  in  accordance  with  the  motor 
manufacturer’s  instructions  provided  as  a  supplement  to  this 
manual.
PRIMARY SYSTEM CONTROL
All XP boiler installations require a “Primary System Control” that 
senses and reacts to water temperature inside the storage tank 
on domestic water applications or in the return line on primary/
secondary  hydronic  heating  systems.  The  Primary  System 
Control will activate and deactivate boiler heating cycles based 
on its setpoint and current system water temperature. There are 
three suitable methods to configure a Primary System Control. 
One of these three methods must be used.
1.  The  Primary  System  Control  can  be  the  boiler’s 
control  system  working  with  the  factory  supplied  Header 
Sensor, installed inside the storage tank on domestic water 
applications  or  in  the  return  line  on  primary/secondary 
hydronic heating systems.
2.  Alternatively,  the  Burner  Control  system  can  be  used 
as a Primary System Control. It will also provide boiler status 
and error reporting. Multiple boilers can be joined together 
to heat a system instead of a single, larger burner or boiler. 
Using boilers in parallel is more efficient, costs less, reduces 
emissions, improves load control, and is more flexible than 
the traditional large boiler.
3.  MB2  and  COM2  ports  can  be  used  for  Building 
Management Systems. 
INTERNAL CONTAMINANTS
The  hydronic  system  must  be  internally  cleaned  and  flushed 
after a new or replacement boiler has been installed, to remove 
contaminants  that  may  have  accumulated  during  installation. 
This is extremely important when a replacement boiler is installed 
into an existing system where Stop Leak or other boiler additives 
have been used.
Failure  to  clean  and  flush  the  system  can  produce  acid 
concentrations  that  become  corrosive,  and  leads  to  heat 
exchanger failure.
All hot water heating systems should be completely flushed with 
a grease removing solution to assure trouble-free opera tion. Pipe 
joint compounds, soldering paste, grease on tubing and pipe all 
tend to contaminate a system
Failure  to  flush  contaminants  from  a  system  can  cause  solids 
to  form  on  the  inside  of  boiler  exchangers,  create  excessive 
blockage  of  water  circulation,  deterioration  of  the  pump  seals 
and impellers.
HOT WATER BOILER SYSTEM - GENERAL WATER 
LINE CONNECTIONS
Piping  diagrams  will  serve  to  provide  the  installer  with  a 
reference for the materials and methods of piping necessary for 
installation. It is essential that all water piping be installed and 
connected  as  shown  on  the  diagrams.  Check  the  diagrams  to 
be used thoroughly before starting installation to avoid possible 
errors and to minimize time and material cost. It is essential that 
all  water  piping  be  installed  and  connected  as  shown  on  the 
diagrams. See Figure 78 on Page 80 and Figure 79 on Page 81.
CLOSED WATER SYSTEMS
Water  supply  systems  may,  because  of  code  requirements 
or  such  conditions  as  high  line  pressure,  among  others,  have 
installed  devices  such  as  pressure  reducing  valves,  check 
valves, and back flow preventers. Devices such as these cause 
the water system to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed 
system the volume of water will increase when it is heated. As the 
volume of water increases there will be a corresponding increase 
in water pressure due to thermal expansion. Thermal expansion 
can cause premature failure (leakage). This type of failure is not 
covered under the limited warranty. Thermal expansion can also 
cause intermittent Temperature-Pressure Relief Valve operation: 
water discharged from the valve due to excessive pressure build 
up.  This  condition  is  not  covered  under  the  limited  warranty. 
The Temperature-Pressure Relief Valve is not intended for the 
constant relief of thermal expansion.
A  properly  sized  thermal  expansion  tank  must  be  installed  on 
all  closed  systems  to  control  the  harmful  effects  of  thermal 
expansion. Contact a local plumbing service agency to have a 
thermal expansion tank installed.
PRESSURE RELIEF VALVE
An ASME rated pressure relief valve is furnished with the boiler. 
A fitting for the relief valve is provided in the top of the boiler. 
Never  operate  the  heating  elements  without  being  certain  the 
boiler  is  filled  with  water  and  a  properly  sized  pressure  relief 
valve is installed in the relief valve opening provided.
The pressure rating of the relief valve should be equal to or less 
than the rated pressure capacity of any component in the system 
including the boiler. Should the valve need to be replaced, call 
the toll free phone number listed on the back of this manual for 
further technical assistance