A.O. Smith VB/VW- 750 User Manual

Page of 52
8
THE CONTROL SYSTEM
The control system consists of four basic components: 
1)  Modulation  Control  Board  (MCB);  2)  Power  Distribution
Board (PDB); 3) Variable Frequency Drive (VFD), see Figure
2; User Interface Module, see Figure 20. The Modulation 
Control Board and the Power Distribution Board are located 
in the control box and can be accessed by opening the front 
door of the unit. The User Interface Module is attached to 
the front door panel. Every system will have one Modulation 
Control  Board  (MCB),  one  Power  Distribution  Board  (PDB),
and  one  User  Interface  Module  (UIM).
The MCB contains dipswitches which are used to configure the
boiler  for several different control options, see the Control System 
Section.
FIGURE 2.
HOT SURFACE IGNITER
The Hot Surface Igniter is a device that ignites the main burner by high 
tempera ture (>1800°F) [982°C], see Figure 3. The igniter is made
of recrystallized silicon carbide, and when 120 VAC is applied to the 
igniter, suf fi cient heat is generated to ignite the main burner. Although
improvements have been made to strength en the igniter, it is still fragile 
and care must be taken in handling the igniter to prevent breakage.
   
 
FIGURE 3. 
FIGURE 4.
PRESSURE SWITCHES
This control system has 3 pressure switches that are standard. Blocked 
Inlet Pressure Switch (BIS), Blower Prover Switch (BPS) Blocked Flue
Switch (BFS).
The BPS on this model is a normally open switch that closes on increased 
vacuum. Once the blower moves enough air to create a vacuum across 
the Venturi the BPS is activated. If the blower fails or cannot move sufficient
air a soft lockout will occur. Inspect the blower for correct operation. 
The Blocked Inlet Switch (BIS) will activate is the intake is blocked only
during the heating cycle. The BIS is a normally closed pressure switch 
that opens when the air intake is blocked. If the BIS is activated check 
and clear the intake of any obstructions. 
The blocked flue pressure switch (BFS) activated when the exhaust
flue of the unit is restricted or blocked. The BFS is a normally closed
switch that opens when positive pressure is placed on the switch 
because of any restriction to the exhaust venting. If the BFS is 
activated check and clear any obstructions causing the restriction.
LOW GAS SWITCH
This VF boiler is available with a low gas pressure switch which 
meets the CSD-1 code requirements, see Figure 5.
The Low Gas Pressure Switch (LGPS) is normally closed and remains
closed unless the pressure falls below the preset pressure.
FIGURE 5. 
LOW GAS PRESSURE SWITCH.
WATER FLOW SWITCH
The  water  flow  switch  is  installed  at  the  boiler  outlet  to
prevent burner operation in the event of inadequate water flow
through the boiler. It is a normally open switch that will close 
its contacts when increasing water flow rate is detected. The
water flow switch is factory-set. The contacts will open when
the flow rate drops below the factory setting causing the gas
valve to close which will turn off the gas to the burner, see 
Figure  6.  Under  no  circumstances  shall  the  flow  switch  be
tampered with or bypassed. Doing so may cause damage to 
the heat exchanger not covered under the warranty. 
FIGURE 6. WATER FLOW SWITCH.
FLAME SENSOR
Each Boiler is equipped with two flame senors coupled together
to detect the presence of the burner flames at high and low fire
conditions. These flame sensors work together as one to sense
the   flame.  If  no  flame  is  sensed,  the  gas  valve(s)  will  close
automatically. If no flame is sensed on three ignition trials, the boiler
will lock out. In the event of a lockout, depress the SELECT button 
on the display board to restart the boiler.
CONTROL COMPONENTS