WATER TEMPERATURE LIMIT CONTROLS
The “V(B/W)” models incorporate an outlet water probe consisting
of two limit controls:
1.  A Manual Reset High limit control that can be set as high as either 
 210°F (99°C) or 235°F (113°C), depending on the application.
2.  A  fixed  manual  high  limit,  factory  set  at  244°F  (118°C).  If 
  the manual reset should open due to high temperature, the  
  gas valves will close and unit will go into lockout. If lockout 
  occurs, push the SELECTION button on UIM to restart boiler.
ON/OFF SWITCH
The ON/OFF Switch is a single-pole, sin gle-throw rocker switch.  
This switch pro vides 120V from the line source to the boiler.
CIRCULATING PUMP
HOT WATER SUPPLY BOILER-VW, the circu lating pump is 
integral to the VW models. This pump has been lu bricated 
at the factory, and future lu brication should be in accordance 
with the motor manufacturer’s instructions provided as a 
supplement to this manual.
HOT WATER HEATING BOILERS-VB, the cir culating pump is NOT 
provided on standard models (optional) and must be obtained and
installed in the field.
NOTE: If a system pump is to be installed on a VB model, 
the maximum rating of pump motor must not exceed 1 hp. 
TEMPERATURE PROBES
INLET / REMOTE 
TEMPERATURE 
PROBE
OUTLET
TEMPERATURE 
PROBE
INLET / REMOTE 
TEMPERATURE 
PROBE
OUTLET TEMPERATURE 
PROBE
FIGURE 7. REMOTE PROBE INSTALLATION.
Temperature probes are 3/4 inch male NPT threaded immersion 
probes, see Figure 7. Temperature probes have embedded 
temperature  sensors  (thermistors). The  boiler’s  control  system
monitors these sensors to determine water temperature at various 
points in the system. 
INLET AND OUTLET TEMPERATURE PROBES
All VF boilers have one Inlet and one Outlet Temperature Probe 
factory installed in the top of the heat exchanger to monitor the 
water temperature entering and leaving the boiler. The Inlet Probe 
is a temperature sensor only and has two leads. The Outlet probe 
also contains the manual reset high temperature limit switch and 
has four leads. The control system displays the Inlet and Outlet 
water temperatures sensed from these two probes on the default 
Temperatures screen.
REMOTE TEMPERATURE PROBE
All VF boilers are supplied from the factory with a Remote 
Temperature Probe. The supplied Remote Temperature Probe 
is used to control system water temperature for a single boiler 
in a domestic hot water storage tank or in the return line from a 
primary/secondary hydronic heating system. Use of the Remote 
Temperature Probe allows a boiler to sense the actual water 
temperature inside the storage tank or hydronic heating loop. 
The boiler will modulate its firing rate in response to the 
actual system temperature and load conditions. The control  
system displays the temperature sensed from the Remote 
Temperature Probe as the “Tank” temperature on the default
Temperatures screen.
QUAD THERMISTOR PROBE
When connecting up to 4 boilers to a single storage tank 
or one primary/secondary hydronic heating system the 
optional Quad Thermistor Probe should be used. The Quad  
Thermistor Probe is a remote temperature probe with four 
temperature sensors embedded in one device. The Quad Thermistor 
Probe allows up to 4 boilers to sense system temperature from 
same point in the system. Use of the Quad Thermistor Probe 
will allow each connected boiler to individually sense actual 
water temperature in the storage tank or hydronic heating loop. 
The temperatures sensed from each of the four temperature 
sensor circuits in a Quad Thermistor Probe are shown as “Tank”
temperature on each boiler’s default Temperatures screen.
NOTE: See the Field Wiring, Remote Temperature Probe 
Installation and the Primary System Control sections of this manual 
for operating and installation instructions.
LOW WATER CUTOFF (OPTIONAL)
If boiler is installed above radiation level, a Low Water Cutoff Device 
must be installed in boiler outlet at time of installation or, order 
pre-installed from the factory. If low water detection is required by 
authorities having jurisdiction, a low water cutoff switch should be 
installed in the boiler outlet water line. The switch should receive 
periodic (every six months) inspection to assure proper operation.
PRESSURE RELIEF VALVE
An ASME rated pressure relief valve is furnished with the boiler. 
Never operate the boiler if it is not filled with water and a properly
sized pressure relief valve is not installed.
The pressure rating of the relief valve should be equal to or less 
than the rated pressure capacity of any component in the system 
including the boiler. Should the valve need to be replaced, call 
the toll free phone number listed on the back of this manual for 
further technical assistance.
Explosion Hazard
Relief Valve must comply with 
ASME code.
Properly sized Relief Valve must 
be installed.
Can  result  in  overheating  and
excessive  tank  pressure.
Can cause serious injury or death.
A discharge pipe from the relief valve should terminate at an adequate 
floor drain. Do not thread, plug, or cap the end of drain line.
CAUTION
• 
Pressure Relief Valve discharge pipe must 
  terminate at adequate drain.
Water Damage Hazard