Burnham 1100-H4 User Manual

Page of 96
7
c.  Horizontal ducts. Minimum free area of one (1) 
square inch per 2,000 Btu per hour input of all 
equipment in space. Duct cross-sectional area 
shall be same as opening free area.
 
Alternate method for boiler located within 
confined space. Use indoor air if two permanent 
openings communicate directly with additional 
space(s) of sufficient volume such that combined 
volume of all spaces meet criteria for unconfined 
space. Size each opening for minimum free area 
of one (1) square inch per 1,000 Btu per hour 
input of all equipment in spaces, but not less than 
100 square inches.
7.  Combustion Air/Ventilation Duct Louvers and 
Grilles. Equip outside openings with louvers to 
prevent entrance of rain and snow, and screens to 
prevent entrance of insects and rodents. Louvers and 
grilles must be fixed in open position or interlocked 
with equipment to open automatically before burner 
operation. Screens must not be smaller than ¼ inch 
mesh.
  Consider the blocking effect of louvers, grilles and 
screens when calculating the opening size to provide 
the required free area. If free area of louver or grille 
is not known, assume wood louvers have 20-25 
percent free area and metal louvers and grilles have 
60-75 percent free area.
II.  Unpack Boiler
CAUTION
Do  not  drop  boiler.    Do  not  bump  boiler  jacket 
against floor.
A.
  Move boiler to approximate installed position.
B.
  Remove all crate fasteners.
C.
  Lift and remove outside container.  Save two of the 
wooden slats from the container sleeve for use in Steps 
E and F.
D.
  Remove all boiler hold-down fasteners.
WARNING
Installation  of  this  boiler  should  be  undertaken 
only  by  trained  and  skilled  personnel  from  a 
qualified service agency.
E.
  Tilt the boiler to its front side or back side and slide a 
wooden slat under the three raised feet.
F.
  Tilt the boiler in the opposite direction and slide 
another wooden slat under the three raised feet.
G.
  Slide the boiler left or right off the skid using the two 
wooden slats as runners.
H.
  Move boiler to its permanent location.
NOTICE
Boilers  operated  with  direct  vent  (sealed 
combustion) are exempt from needing provisions 
for  combustion  air  from  the  room,  provided 
air  intake  piping  is  installed  per  Code  and  the 
instructions in the manual.
6.  For boiler located within unconfined space in building 
of unusually tight construction or within confined 
space, provide outdoor air through two permanent 
openings which communicate directly or by duct 
with the outdoors or spaces (crawl or attic) freely 
communicating with the outdoors. Locate one opening 
within twelve (12) inches of top of space. Locate 
remaining opening within twelve (12) inches of bottom 
of space. Minimum dimension of air opening is three 
(3) inches. Size each opening per following:
a.  Direct communication with outdoors. Minimum 
free area of one (1) square inch per 4,000 Btu per 
hour input of all equipment in space.
b.  Vertical ducts. Minimum free area of one (1) 
square inch per 4,000 Btu per hour input of all 
equipment in space. Duct cross-sectional area 
shall be same as opening free area.
CAUTION
If  using  indoor  air  for  combustion  (see  Venting  Section  -  Indoor  Air),  avoid  operating  this  boiler  in  an 
environment where saw dust, loose insulation fibers, dry wall dust, etc. are present.  If boiler is operated 
under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper 
operation.