Crown Boiler CWI172 User Manual

Page of 56
36
Heat Exchanger Cleaning Procedure
1) Turn off electrical power and gas supply to the boiler.
2) Disconnect the damper and vent connector from the boiler.
3)    Remove the upper front and top jacket panels. If possible, remove the rear and left side jacket panels.
4) Remove the burners.
5) Remove the blocked vent (“spill”) switch.
6) Remove the ¼-20 nuts and washers holding the flue collector onto the heat exchanger.
7) Carefully remove the flue collector gasket strips and set them aside.
8) Remove the flue collector from the heat exchanger.
        9) Clean the flue passageways using a stiff bristle brush. Be certain that all foreign material is removed from the gaps
between the pins.
10) Clean the bottom surfaces of the heat exchanger.
11) Put a light in the combustion chamber and look through the flue passages from the top to verify that they have been
thoroughly cleaned.
12) Replace the flue collector gasket strips. If desired, RTV silicone sealant with a 500F intermittent duty temperature may be
substituted for this rope gasket. The flue collector must be thoroughly sealed to the heat exchanger.
13) Replace the ¼-20 nuts and washers that hold down the flue collector.
14) Reattach all the jacket components.
15) Reinstall burners, being careful to put the pilot main burner in its original location.
16) Replace the blocked vent switch.
17)  Reconnect the damper and vent system.
WARNING
SOOT  DEPOSITS  IN  THE  FLUE  PASSAGES  ARE  A  SIGN  THAT  THE  BOILER  MAY  BE  OPERATING  AT  HIGH
CARBON  MONOXIDE  (CO)  LEVELS.   AFTER  CLEANING  THE  BOILER  OF  SOOT  DEPOSITS,  CHECK  THE  CO
LEVEL  IN  THE  FLUE  GAS  TO  INSURE  THAT  THE  BOILER  IS  OPERATING  PROPERLY.
   If it is necessary to check CO, use a combustion analyzer, or other instrument which is designed to measure CO in flue gas.
A CO “sniffer” designed for testing CO levels in ambient air cannot be used to check boiler combustion. Take a flue gas
sample by inserting a sample probe through the draft diverter opening and into the flue collector so that the sample is taken
in the area directly over the heat exchanger. Do not take a sample until the boiler has been firing for at least five minutes.
   A normal CO reading for a CWI series boiler is less than 50ppm (0.005%). A reading of more than 100ppm (0.01%) is
indicative of a combustion problem.
   Some causes of excessive CO include:
Incorrectly sized main burner orifice for the altitude at which boiler is installed
Crooked or out-of-round orifice holes (never attempt to drill orifice for this boiler in the field)
Partially plugged flue passages
Improper manifold pressure
Foreign material in burner venturis or burner ports
Leak in seal between flue collector and heat exchanger
Inadequate supply of combustion air
35