Cape Cod Wood Stove
R
INSTALLATION
MASONRY CHIMNEY
For optimal performance, masonry chimneys 
used  to  vent  this  appliance  should  be  lined  with 
a 6" stainless steel liner.  Installations into a clay 
flue  without  a  stainless  steel  liner  may  reduce 
efficiency, cause the glass to darken, and produce 
excessive creosote.
Ensure  that  a  masonry  chimney  meets  the 
minimum standards of the National Fire Protection 
Association  (NFPA)  Standard  211.  It  must  have 
at  least  a  5/8"  (16mm)  fire  clay  liner  or  a  listed 
chimney  liner  system.  See  Figure  8.  Make  sure 
there are no cracks, loose mortar or other signs of 
deterioration and blockage.  It is best to have the 
chimney inspected by a professional and be sure 
to  have  the  chimney  cleaned  before  the  stove  is 
installed and operated. 
The flue should be checked to determine that it 
is  not  too  large  for  the  stove.  NFPA  211  allows 
the cross-sectional area of the flue to be no more 
than  3  times  the  cross-sectional  area  of  the  flue 
collar of the stove (28 x 3 = 84 square inches).  It is 
recommended that a chimney with a larger diameter 
be relined, since the oversized flue can cause poor 
performance and contribute to the accumulation of 
creosote.  (See page 36 for more information about 
troubleshooting draft problems).  
NOTE;  Never install more than one appliance 
to any chimney.
When connecting the stove through a combus-
tible wall to a masonry chimney, special methods 
are  needed.    There  are  several  ways  to  make 
this  connection,  including  the  construction  of  a 
masonry thimble.  This installation shall conform to 
CAN/CSA-B365.  Check with your local building 
authorities or consult the National Fire Protection 
Association  (NFPA  211).    Refer  to  Figure  9  (on 
page 15) and Figures 10 & 11 (on page 17).
FIGURE 8
Thimble Assembly:
12" (305mm) of brick 
separation between clay 
liner and combustibles.
Fireclay liner 5/8" 
(16mm) Minimum or 
Equivalent.
Sill support
Header
Wood Stud 2" 
(51mm) 
Clearance from 
chimney wall
Fireclay liner 5/8" 
(16mm) Minimum or 
Equivalent.