Cape Cod Wood Stove
R
First, make the frame for the thimble, ensuring 
it is no smaller than 14" square, to maintain a 2" air 
space  around  the  chimney  section.   Attach  the  wall 
spacer to the chimney side of the frame.  Then insert 
the frame into the opening, toe nailing it to the wall 
studs.  Install the wall band in the framing to secure 
the chimney section in place.  Insert a single section of 
chimney connector into the chimney through the wall 
band, being sure it does not protrude into the chimney 
beyond the edge of the chimney flue lining.  Apply 
high  temperature  furnace  cement  to  the  end  of  the 
chimney  section  and  install  it  over  the  connector, 
through  the  wall  spacer.   Tighten  the  wall  band  to 
hold the chimney section firmly in place and against 
the  chimney.    Install  the  trim  collar  on  the  outside 
of  the  opening.    Check  to  ensure  there  is  a  1"  air 
space between the connector and the chimney section.  
During installation ensure that a 2" air space to the 
wood framing is maintained.  Do not fill this space with 
insulation.  Insulation in this air space will cause a heat 
buildup which may ignite the wood framing.
INSTALLATION
MASONRY CHIMNEY
Add  center-line  measurement  to  the  depth  of  your  floor  protector.  
Mark this combined measurement at the correct wall location for your 
installation,  maintaining minimum clearance to combustibles, and mark 
the wall for a 10" x 10" (254mm x 254mm) square hole. The center of 
the square hole should line up with the centerline of the rear vent flue 
pipe, as shown in Figure A above.
For  the  method  of  installation  to  a  masonry 
chimney shown in Figures 10 & 11, (on page 17), 
it  will  be  necessary  to  purchase  an  8  inch  inside 
diameter, 12 inch long section of prefabricated listed 
solid pack chimney to use as a thimble.  Purchase a 
wall spacer, trim collar and a wall band manufactured 
to fit the chimney section you purchase.
The safety features of this system are twofold:  
1) A 2" air space between the chimney section and 
combustible wall; and, 2) The 1" air space around the 
chimney connector as it passes through the chimney 
section to the chimney.
The location of the opening through the wall 
to the chimney must leave a minimum 18" vertical 
clearance between the connector pipe and the ceiling 
to prevent the ceiling from catching fire.
Measure as shown in Figure A below and cut  
an opening in the wall large enough to accommodate 
the outside dimension of the chimney section plus 
the minimum air space specified by its manufacturer.  
It may be necessary to cut the wall studs and install a 
header and a sill frame to maintain the wall support.  
The hole in the chimney must have at least an 8" 
diameter fire clay liner or equivalent secured with 
refractory  mortar.    If  it  is  necessary  to  cut  a  hole 
in  the  chimney  liner,  use  extreme  care  to  keep  it 
from shattering.
FIGURE A
Center of Hole
Wall
Center Line
Opening
Center Line