Sherwood EG40 DV User Manual

Page of 39
31
Trouble Shooting
Problem
Possible Cause
Solution
The  main  burner  does  not 
ignite when called for.
The gas valve may not be on.
• Check that the gas control knob is in the “ON” position.
Thermostat is not calling for 
heat.
• Adjust the thermostat several degrees above ambient 
temperature.
Problem with gas valve.
• Use a DC voltmeter to measure the voltage across the 
TPTH and TP terminals. Main operator voltage: Open 
circuit ≥ 325mV Closed circuit ≥ 100mV
• If voltage is not present, check the control circuit for 
proper operation.
• If proper control system voltage is present, replace the 
gas control.
Spark will not light the pilot 
after repeatedly pressing the 
spark ignitor.
Defective piezo ignitor.
• Check connections to ignitor.
• If ignitor connections are good but no spark, replace 
ignitor.
Broken spark electrode.
• Check for broken ceramic insulation, replace electrode if 
broken.
Misaligned spark electrode.
• If spark is not arcing from electrode to pilot, loosen the 
screws on the pilot base adjust and tighten.
Pilot will not remain lit.
Problem with thermocouple 
circuit.
• Check for proper connection of the thermocouple to the 
rear of the valve. If loose, fully tighten.
• Check pilot for full flame impingement around 
thermocouple.  If flame is too small, check gas pressure, 
adjust pilot rate screw, check pilot head for damage.
• Check thermocouple voltage at valve. It must be greater 
than 5 mV.  If low, replace thermocouple.
Air in gas line (pilot dies while 
knob is depressed).
• Bleed line.
• Check gas line pressure.
• Contact dealer.
Burners will not remain lit.
Problem with thermopile 
circuit.
• Check gas line pressure .
• Check for flame impingement on thermopile. If low, see 
“Pilot will not remain lit”.
• Check thermopile for minimum of 300 mV when burner is 
switched on.
• Check wiring to thermostat for breaks.
Flame lifting
Leak in vent pipe
• Check for leaks in vent connections.
Improper vent configuration
• Check vent configuration with manual.
Terminal may be recirculating 
flue gases
• Check to see if terminal is on correctly.
• May need to install high wind termination cap.
• Contact dealer.
Glass fogs up
Normal Condition: after the appliance warms up the glass will clear.
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
Blue Flames
Normal during start up: flames will yellow as the fireplace heats up.
Flames are burning “dirty” or 
sooting
Flame impingement
• Check log positioning.
• Increase primary air by opening the venturi shutter and/
or by opening the vent restrictor.
See also “Burners will not remain lit.”
Remote control doesn’t work
Problem with the remote
• One or more of the batteries are dead. See remote 
control instructions.
Problem with fireplace
• The on/off switch is turned to OFF.
• The gas control valve is turned to PILOT or OFF.
• The pilot has gone out.