Do  not  subject  the  combination  gas  valve  to  inlet  gas  
pressures  of  more  than  14.0”  W.C.  -  natural  gas.   A  service 
regulator is necessary if higher gas pressures are encountered.
Manifold gas pressure in inches of water column is 3.5.
The  gas  pressure  specified  refers  to  flow  pressure  taken  at 
pressure tap of automatic gas valve while heater is operating.
HEATER WIRING
All electrical work must be installed in accordance with the latest 
version  of  the  National  Electrical  Code ANSI/NFPA  No.  70,  
FIGURE 10 - SINGLE UNIT WIRING DIAGRAM
must conform to all local code authority having jurisdiction. 
 AN 
ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF 
ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION.
If any of the original wire as supplied with the appliance must be 
replaced, use only type 105
0
C thermoplastic or equivalent.  250
0
type F must be used for the flame sensor leads and the spark 
ignition cable must be high voltage 250
0
C.
Figures  shown  are  valid  for  0-2000  ft.  installations.  See 
“HIGH ALTITUDE INSTALLATIONS” for deration requirements  
over 2000 ft.