INSTALLATION DIAGRAMS
GENERAL
The  type,  size  and  location  of  the  relief  valves  must  be  in 
accordance with local codes.  The locations of the relief valves 
shown in the installation diagrams are typical.  The heater has a 
factory installed high temperature limit switch and temperature 
and pressure relief valve.
Cold water lines to heater should be installed as shown in order 
to minimize gravity circulation of hot water to building cold water 
lines.
A listed temperature and pressure relief valve of adequate capacity 
is installed on the heater.  The locations shown in the installation 
diagrams on the following pages are typical.
The  discharge  opening  of  the  temperature  and  pressure  relief 
valve,  located in front of the heater must be piped to an open drain 
and should not be subject to freezing temperatures.
Install in accordance with all local codes.
 
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE 
TEMPERATURE AT FIXTURES.  SEE WATER TEMPERATURE 
CONTROL WARNING ON PAGE 20.  IF HIGHER PREHEAT 
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE 
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT 
WATER SUPPLIED TO FIXTURES.