Lochinvar CG200 User Manual

Page of 28
21
NOTE:
1.  Remove main burners from unit.
2.  Check  that  burner  venturi  and  ports  are  free  of  foreign 
debris.
3.  Clean  burners  with  bristle  brush  and/or  vacuum  cleaner  
- DO NOT distort burner ports or pilot location.
4.  Reinstall burners in unit.  Make sure front and rear of burners 
are installed correctly in burner support brackets.
Also check for good flow of combustion and ventilating air to the 
unit.  Maintain a clear area around the heater at all times.
GAS VALVES
Figure 13 shows the type of combination manual gas control valve 
and regulator used on these heaters.
If  the  gas  valve  becomes  defective,  repairs  should  not  be 
attempted. A  new  valve  should  be  installed  in  place  of  the 
defective one.
FIGURE 13
CHECKING THE INPUT
For  appliance  installation  locations  with  elevations  above  
2000 feet, refer to HIGH ALTITUDE INSTALLATIONS section of 
this manual for input reduction procedure.
1.  Attach a pressure gauge or a manometer to the gauge port 
and  refer to the GAS PRESSURE REGULATOR section for 
correct manifold pressure.
2.  Use this formula to “clock” the meter.  Be sure that other gas  
consuming appliances are not operating during this interval.
  3600  X  H  =  Btuh
     T
  T  =  Time in seconds to burn one cubic foot of gas.
  H = Btu’s per cubic foot of gas.
  Btuh = Actual heater input.
  Example: 
  T  =  15.1 seconds
  H  =  1050 Btu
  Btuh  =  ?
  19  X  1050  = 199,999 Btuh
Should it be necessary to adjust the gas pressure to the burners 
to obtain the full input rate, the steps below should be followed:
3.  Remove  the  regulator  adjustment  sealing  cap,  see  
Figure 13, and adjust the pressure by turning the adjusting 
screw with a screwdriver.
 
 Clockwise to increase gas pressure and input rate.
 
 Counterclockwise to decrease gas pressure and input        
 rate.
4.  “Clock” the meter as in step 2 above.
5.  Repeat steps 3 and 4 until the specified input rate is achieved.
6.  Turn the gas control knob to PILOT.  Remove the pressure 
gauge and replace the sealing cap and the allen wrench set 
screw in the pressure tap opening.
 WARNING
UNDER NO CIRCUMSTANCES SHOULD THE GAS INPUT 
EXCEED THE INPUT SHOWN ON THE HEATER MODEL AND 
RATING PLATE.  OVERFIRING COULD RESULT IN DAMAGE 
OR SOOTING OF THE HEATER.
When the heater is operating at full capacity, or full gas input, it 
should consume 1 cu. ft. of gas in time indicated on Table 3.
TABLE 3
APPROXIMATE TIME REQUIRED TO CONSUME
1 CU. FT. OF GAS AT FULL CAPACITY
  
 
  
 
 
TIME REQ’D
  INPUT 
TYPE 
BTUH 
TO CONSUME
  RATE 
OF 
PER 
1 CU. FT.
  (BTUH) 
GAS 
CU. FT. 
OF GAS
  154,000 
NATURAL 
1050 
24.5 SEC.
  199,000 
NATURAL 
1050 
19.0 SEC.
Figures shown are valid for 0-2000 ft.(0-610m) installations.   See 
“HIGH ALTITUDE  INSTALLATIONS”  for  deration  requirements 
over 2000 ft.(610m).
VENTING SYSTEM
Examine the venting system every six months for obstructions 
and/or deterioration of the vent piping.
Remove all soot or other obstructions from chimney which will 
retard free draft.
REMOTE STORAGE TANK 
TEMPERATURE CONTROL
The water temperature in the storage tank (if used) is controlled 
by the storage tank temperature control.  The sensing element is 
mounted in the hot water storage tank, see page 17.
A change in water temperature in the storage tank lower than 
the  tank  temperature  control  setting  will  cause  the  sensor  to 
activate the circulating pump.  The pump then circulates the water 
through the heater where the thermostat senses the drop in water 
temperature and activates main burner operation of the appliance.
If the storage tank temperature control is out of calibration, replace 
with new control.
 WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL 
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL 
VALVE TO THE APPLIANCE.