Example 2:
If initial inspection after 6 months shows 2” of lime accumulation.
Therefore, the heater should be delimed every 3 months.
FIGURE 14
DELIMING SOLVENTS
Hydrochloric base acids are not recommended for use on glass 
lined tanks.
 
CAUTION
Observe handling instructions on label of product being used. 
TANK CLEANOUT PROCEDURE
The following practices will ensure longer life and enable the unit 
to operate at its designed efficiency:
1.  Once a month the heater should be flushed. Open drain valve 
and allow two gallons of water to drain from the heater. Inlet water 
valve should remain open to maintain pressure in tank.
2.  A cleanout opening is provided for periodic cleaning of the tank. 
Gas must be shut off and heater drained before opening cleanout.
To clean heater through cleanout opening, proceed as follows:
1.  Drain heater.
2.  Remove outer cover plate from lower side of heater jacket.
3.  Remove six (6) hex head screws securing tank cleanout plate 
and remove plate.
4.  Remove lime, scale, or sediment using care not to damage the 
glass lining.
5.  Inspect cleanout plate gasket, if new gasket is required, replace 
with part no. 9004099215.
6.  Install  cleanout  plate.    Be  sure  to  draw  plate  up  tight  by 
tightening screws securely.
7.  Replace outer jacket cover plate. 
In some water areas the sediment might not be removed by this 
method and may result in the water heater making rumbling or 
boiling noises.
IGNITION MODULE SYSTEM
Before calling your service agent, the following checklist should 
be examined to eliminate obvious problems from those requiring 
replacement or servicing.
— Check that “main manual gas shutoff valve” is fully open and 
that gas service has not been interrupted.
— Check  that  after  following  the  appliance  OPERATING 
INSTRUCTIONS, the “Top Knob” of the appliance gas valve 
is in “ON” position.
— Check electrical supply to the appliance for possible blown (or 
tripped) fusing or power interruption.
— Is  the  water  temperature  in  tank  below  the  thermostat  dial 
setting on the appliance thermostat (calling for heat)?
— It is possible that the high limit (E.C.O.) has functioned to shut 
off  the  appliance.    See  FEATURES  —  Water Temperature 
Control for reset procedure.  Contact your serviceman if limit 
continues to function to shut off appliance. 
SYSTEM DIAGNOSTICS
Your  water  heater  is  equipped  with  an  ignition  module  that 
incorporates  a  diagnostic  system  to  assist  in  troubleshooting 
the appliance.  The indicator codes on the ignition module are 
as follows:
1 flash
 System lockout (retries or cycles exceeded)
2 flashes
Pressure switch stuck close
3 flashes
Pressure switch stuck open
4 flashes
Open on high temperature limit switch (eco)
6 flashes
115 volt AC power reversed (check polarity)
7 flashes
Low  flame  sense  signal  (make  sure  flame 
sensor is in burner flame)
8 flashes
Check ignitor
continuous flash -> continuous flame sensed > 5 seconds without 
gas valve
continuous on -> internal control failure - replace ignition control 
module.
Use this diagnostic system in conjunction with the “OPERATIONAL 
CHECKLIST”  and  the  “SEQUENCE  OF  OPERATION”  to 
troubleshoot the appliance.