Lochinvar CG200 User Manual

Page of 28
26
OPERATIONAL CHECKLIST
This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERATION” should be used as an on-the-job 
troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction. Because improper 
piping and wiring can result in unsatisfactory system performance, it is suggested that the installation be examined before using the 
checklist.  Be sure to refer to the correct piping and wiring diagram for the type of system that is installed.
The system should be filled with water, purged of air, valves properly set and utilities connected and ready to operate.
   
 
                                                   
REMEDY
  COMPLAINT 
                CAUSE 
                     USER 
                     SERVICEMAN
*Water not hot enough. 
Thermostat set too low. 
Set thermostat dial to a higher
  
 
temperature.
   
Thermostat out of calibration. 
Call serviceman 
Recalibrate thermostat. If thermostat cannot
   
 
 
be recalibrated, replace.
*Insufficient hot water 
Thermostat set too low. 
Set thermostat dial to a higher
*See WATER TEMPERATURE   
temperature.
CONTROL WARNING (on 
Page 20). 
Thermostat out of calibration. 
Call serviceman. 
Recalibrate thermostat. If thermostat cannot
   
 
 
be recalibrated, replace.
   
Main manual gas shutoff 
Open main manual gas shutoff 
   
valve partially closed. 
valve to fullest extent. 
 
   
Heater too small for demand. 
Space usage to give heater time
   
 
to restore water temperature. 
 
   
Thermostat differential is 
Call serviceman. 
Replace dual bulb controller if differential is
   
too wide. 
 
greater than 4°F.
   
Heater recovery is slower. 
Call serviceman. 
Check gas input. If incorrect, adjust gas
   
 
 
pressure or replace main burner orifice.
   
Drafthood not installed or 
Call serviceman. 
Install drafthood or baffles as furnished 
   
one or more flue baffles. 
 
with unit.
Water temperature too hot. 
Thermostat set too high. 
Set thermostat to a lower setting. 
Heater makes sounds: sizzling.  Condensation on outside
   
of tank, normal. 
 
 
Rumbling. 
Sediment accumulation on 
Drain a quantity of water through 
Delime heater.
   
bottom of tank. 
drain valve. If rumbling persists,
   
 
call a serviceman.
Ticking or metallic sounds. 
Expansion and contraction- 
   
normal.
Pounding. 
Air chambers in piping have 
Drain piping system and refill.
   
become waterlogged. 
Heater must be off while this is
   
 
being done.
Combustion noises. 
Too much primary air. 
Adjust shutters. 
   
Overfired heater; Incorrect 
Call serviceman. 
Check and correct as necessary.
   
burners or orifice for type
   
of gas used.
Water leaks. 
Drain valve not closed 
If drain valve cannot be closed
   
 tightly. 
tightly, replace.
   
If leakage source cannot 
Shut off gas supply to heater 
Repair or in case of suspected tank leakage,
   
be corrected or identified, 
and close cold water inlet valve 
be certain to confirm before replacing heater.
   
call serviceman. 
to heater.
Gas odors. 
Heater is overfired. 
Shut off gas supply to heater 
Check for sooted flue passage.
   
 
and call a serviceman.
   
 
 
Check for obstructed vent line.
   
 
 
Check backdraft or lack of draft.
   
Possible gas leaks. 
Shut off gas supply to heater and
   
 
call gas company at once.