Lochinvar CG200 User Manual

Page of 28
25
SEQUENCE OF OPERATION FLOW CHART
Description of this flow chart can be found in the “SEQUENCE OF OPERATION” section found on page 18.
Switch power on
to unit.
Thermostat calls
for heat.
Ignition Control
Board performs
diagnostic check on
components
Ignition Control
Board sends power
to Exhaust Inducer
Exhaust Inducer
engages Prover
Switch
Ignition Control
Board provides
power to Silicon
Nitride Ignitor
Silicon Nitride
Ignitor
warms up for
20 seconds
Ignition
Control Board
opens Gas
Valve.
Ignition Control 
Board shuts off
Silicon Nitride
Ignitor after
3 seconds
Ignition Control
Board waits 3 more 
seconds to 
monitor Flame
Sensor.
Did Main 
Burner Light?
YES
Ignition Control
Board monitors
units until T’Stat
is satisfied. 
Ignition Control
Board shuts off Gas
Valve and allows the 
Exhaust Inducer to 
purge appliance for 
20 seconds.
NO