INSTALLATION INSTRUCTIONS
REQUIRED ABILITY
INSTALLATION  OR  SERVICE  OF  THIS  WATER  HEATER  
REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED 
TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, 
VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE REQUIRED.
 
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT 
IN SERIOUS PERSONAL INJURY OR DEATH.
UNCRATING
The heater is shipped with the inducer already installed. The wiring 
conduit runs from the thermostat to the inducer. Before turning unit on, 
check to make sure wiring conduit is securely plugged into the inducer. 
LOCATING THE HEATER
  
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH 
AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER 
AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR 
ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, 
OPERATED OR REPAIRED.  FLAMMABLE VAPORS ARE HEAVY 
AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE 
HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE 
OR EXPLOSION.  SOME LOCAL CODES PERMIT OPERATION OF 
GAS APPLIANCES IN SUCH AREAS IF THEY ARE INSTALLED 
18” OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE 
RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A 
CARPETED FLOOR.  A FIRE HAZARD MAY RESULT. Instead the 
water heater must be placed on a metal or wood panel extending 
beyond the full width and depth by at least 3 inches in any direction.  
If the heater is installed in a carpeted alcove, the entire floor shall 
be covered by the panel. Also, see the DRAINING requirements 
in MAINTENANCE Section.
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS 
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
 WARNING
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY 
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST 
NEVER BE PLACED ON OR ADJACENT TO THE HEATER.  OPEN 
CONTAINERS OR FLAMMABLE MATERIAL SHOULD NOT BE 
STORED OR USED IN THE SAME ROOM WITH THE HEATER.
When  installing  the  heater,  consideration  must  be  given  to 
proper  location.  Location  selected  should  be  as  close  to  the 
stack or chimney as practicable, with adequate air supply and as 
centralized with the piping system as possible.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE 
IT WILL BE SUBJECT TO FREEZING.
LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE 
LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER 
OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE 
ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE. 
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE 
DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER.
 
 Such 
pans should be fabricated with sides at least 2” deep, with length and 
width at least 2” greater than the diameter of the heater and must be 
piped to an adequate drain.  The pan must not restrict combustion air flow.
For  appliance  installation  locations  with  elevations  above  
2000 feet (610m), refer to HIGH ALTITUDE INSTALLATIONS 
section of this manual for input reduction procedure.
LEVELING
If the unit is not level, insert the bolts which were used in crating 
into the legs to correct this condition.
CLEARANCES
These heaters are approved for installation on combustible flooring 
in an alcove when the minimum clearance from any combustion 
construction are followed as indicated in figure 6. 
In all installations the minimum combustible clearances from vent 
piping shall be 6”. Vent piping passing through a combustible wall 
or ceiling must be a continuous run (no joints) and retain the 6” 
clearance unless an approved reducing thimble is used.
A service clearance of 24” should be maintained from serviceable 
parts, such as relief valves, flue baffles, thermostats, cleanout 
openings or drain valves.
The units are approved for installation with side, rear and ceiling 
clearances.
HARD WATER
Where hard water conditions exist, water softening or threshold type 
of water treatment is recommended. This will protect dishwashers, 
coffee urns, water heaters, water piping and other equipment.
See MAINTENANCE section for details of tank cleanout procedure.
CLOSED WATER SYSTEMS
Water  supply  systems  may,  because  of  code  requirements 
or  such  conditions  as  high  line  pressure,  among  others,  have 
installed  devices  such  as  pressure  reducing  valves,  check 
valves, and back flow preventers. Devices such as these cause 
the water system to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed 
system the volume of water will grow when it is heated. As the 
volume  of  water  grows  there  will  be  a  corresponding  increase 
in water pressure due to thermal expansion. Thermal expansion 
can cause premature tank failure (leakage). This type of failure 
is  not  covered  under  the  limited  warranty.  Thermal  expansion 
can also cause intermittent Temperature-Pressure Relief Valve 
operation:  water  discharged  from  the  valve  due  to  excessive 
pressure build up. This condition is not covered under the limited 
warranty. The Temperature-Pressure Relief Valve is not intended 
for the constant relief of thermal expansion.
A  properly  sized  thermal  expansion  tank  must  be  installed  on 
all  closed  systems  to  control  the  harmful  effects  of  thermal 
expansion. Contact a local plumbing service agency to have a 
thermal expansion tank installed.
AIR REQUIREMENTS
REFER TO THE LATEST EDITION OF THE “NATIONAL FUEL 
GAS CODE” ANSI Z223.1/NFPA 54.
KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE 
MATERIALS, GASOLINE AND OTHER FLAMMABLES, 
VAPORS AND LIQUIDS.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR 
VENTILATING AIR.
 WARNING
FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR 
COMBUSTION AND VENTILATION.  AN INSUFFICIENT SUPPLY 
OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION 
PRODUCTS RESULTING IN AIR CONTAMINATION THAT 
MAY BE HAZARDOUS TO LIFE.  SUCH A CONDITION OFTEN 
WILL RESULT IN A YELLOW, LUMINOUS BURNER FLAME,