Lochinvar CG200 User Manual

Page of 28
7
CAUSING CARBONING OR SOOTING OF THE COMBUSTION 
CHAMBER, BURNERS AND FLUE TUBES AND CREATES A 
RISK OF ASPHYXIATION.
Where  an  exhaust  fan  is  supplied  in  the  same  room  with  a 
heater, sufficient openings for air must be provided in the walls.  
UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN 
INTO THE ROOM THROUGH THE CHIMNEY, CAUSING POOR 
COMBUSTION.  SOOTING MAY RESULT IN SERIOUS DAMAGE 
TO THE HEATER AND RISK OF FIRE OR EXPLOSION.
UNCONFINED SPACE
In buildings of conventional frame, brick, or stone construction, 
unconfined  spaces  may  provide  adequate  air  for  combustion, 
ventilation and draft hood dilution.
If the unconfined space is within a building of tight construction 
(buildings  using  the  following  construction:  weather  stripping, 
heavy insulation, caulking, vapor barrier, etc.), air for combustion, 
ventilation and draft hood dilution must be obtained from outdoors.  
The  installation  instructions  for  confined  spaces  in  tightly 
constructed buildings must be followed to ensure adequate air 
supply.
CONFINED SPACE
When  drawing  combustion  and  dilution  air  from  inside  a 
conventionally constructed building to a confined space, such a 
space shall be provided with two permanent openings, ONE IN 
OR WITHIN 12 INCHES OF THE ENCLOSURE TOP AND ONE 
IN OR WITHIN 12 INCHES OF THE ENCLOSURE BOTTOM.  
Each opening shall have a free area of at least one square inch 
per 1000 Btuh of the total input of all appliances in the enclosure, 
but not less than 100 square inches.
If  the  confined  space  is  within  a  building  of  tight  construction, 
air for combustion, ventilation, must be obtained from outdoors.  
When directly communicating with the outdoors or communicating 
with  the  outdoors  through  vertical  ducts,  two  permanent 
openings,  located  in  the  above  manner,  shall  be  provided.  
Each  opening  shall  have  a  free  area  of  not  less  than  one 
square  inch  per  4000  Btuh  of  the  total  input  of  all  appliances 
in  the  enclosure.    If  horizontal  ducts  are  used,  each  opening 
shall  have  a  free  area  of  not  less  than  one  square  inch  per  
2000 Btuh of the total input of all appliances in the enclosure. 
VENTING
 
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST 
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR 
RECIRCULATION OF FLUE GASES.  SUCH CONDITIONS 
CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
Heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will 
retard a free draft.
Type B venting is recommended with these heaters. 
This  water  heater  must  be  vented  in  compliance  with  all  local 
codes,  the  current  revision  of  the  National  Fuel  Gas  Code  
(ANSI-Z223.1) and with the Category I Venting Tables.
If  any  part  of  the  vent  system  are  exposed  to  ambient 
temperatures  below  40°F  (4°C)  it  must  be  insulated  to 
prevent condensation.
The  following  steps  shall  be  followed  with  each  appliance 
connected  to  the  venting  system  placed  in  operation,  while 
any other appliances connected to the venting system are not 
in operation.
1.  Seal any unused openings in the venting system.
2.  Inspect the venting system for proper size and horizontal pitch, 
as  required  in  the  National  Fuel  Gas  Code, ANSI  Z223.1.  
Determine  that  there  is  no  blockage  or  restriction,  leakage, 
corrosion and other deficiencies which could cause an unsafe 
condition.
3.  So far as is practical, close all building doors and windows 
and all doors between the space in which the water heater(s) 
connected to the venting system are located and other spaces 
of the building.  Turn on all appliances not connected to the 
venting system.  Turn on all exhaust fans, such as range hoods 
and bathroom exhausts, so they shall operate at maximum 
speed. Close fireplace dampers.
4.  Follow the lighting instruction.  Place the water heater being 
inspected in operation.  Adjust thermostat so appliance shall 
operate continuously.
5.  After it has been determined that each appliance connected 
to the venting system properly vents when tested as outlined 
above, return doors, windows, exhaust fans, fireplace dampers 
and any other gas burning appliance to their previous conditions 
of use.
6.  If improper venting is observed during any of the above tests, 
the venting system must be corrected.
 
WARNING
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR 
CONTAMINATION AND UNSAFE CONDITIONS.
•   If the back draft cannot be corrected by the normal method or 
if a suitable draft cannot be obtained, a blower type flue gas 
exhauster  must  be  employed  to  assure  proper  venting  and 
correct combustion.
•  Do not connect the heater to a common vent or chimney with 
solid  fuel  burning  equipment. This  practice  is  prohibited  by 
many local  building codes as is the practice of venting gas 
fired equipment to the duct work of ventilation systems.
FIGURE 6 - ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES IN AN ALCOVE