TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS
3
62-0311—13
Table 2. Applications and Features
Fig. 1. Dimensions in inches (mm).
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.
3. Installer must be a trained and experienced service 
technician.
WARNING
Risk of electrical shock.
Can cause severe injury, property damage or 
death.
Disconnect power supply before installation and 
before servicing.
IMPORTANT
The thermostats are line voltage powered devices. All 
wiring must comply with national and local electrical 
codes, ordinances and regulations. Provide disconnect 
means and overload protection, as required.
The TB8575A1016 thermostat must be powered by an 
Approved 24 Vac, Class 2, NEMA rated transformer 
(such as a W6380 Relay Control Center).
Location
The thermostats are the temperature control element in a 
fan coil or air-conditioning system. They must be located 
about 1.5m (5 ft.) above the floor, in a position with good 
air circulation, to sense room temperature.
IMPORTANT
Do not mount the device where it can be affected by:
1. Drafts or dead spots behind doors or in corners.
2. Hot or cold air from ducts.
3. Radiant heat from the sun or appliances.
4. Unheated (uncooled) areas such as an outside 
wall behind the thermostat.
5. Concealed pipes or chimneys.
Mounting and Wiring
CAUTION
Equipment damage hazard.
Operation at low temperatures can cause fan 
coil damage.
This thermostat is not a safety device. Do not use 
it where the space temperature is outside of the 
device operating range.
A display of two dashes, – –, for the Room Temp 
display indicates a sensor failure or a temperature 
outside of the thermostat operating range of 18°C 
to 49°C (0°F to 120°F). With – – displayed, the 
thermostat ceases to operate. When the 
temperature returns to within its operating limits, 
the thermostat returns to operation.
The optional freeze protect feature should be used 
if low temperatures can occur.
The thermostat must be mounted flush to the wall. The 
thermostat can be mounted directly to a 2 x 4 in. 
horizontal junction box (see Fig. 2 on page 4). An optional 
Models
Applications
Features
Heat/Cool/
Auto
Pipes Voltage
Number
of Relays
a
a
The five relays are wired via terminals W, Y, Gh, Gm, and Gl. Relay 1 controls Heat open (W) or Cool open (Y). Relay 
2 controls Cool open or Electrical heater output (Y/A). Relays 3, 4, and 5 control the High, Medium, and Low fan 
speeds respectively (Gh, Gm, and Gl). 
NOTE: In 2-pipe configurations without Auxiliary Heat, only 4 relays are used; relay 2 (Y/A) is not used.
Energy
Savings
Input
Fan: On, 
Auto, or 3 
speed
Manual/
Auto
Changeover
Remote
Sensor
Back
 Light
Pipe
Sensor
b
b
Pipe sensor is required for 2 pipe auto changeover and 2 pipe auxiliary heat applications.
TB6575A1016 All
2 or 4 120 or 
240 Vac
5
Yes
Yes
Yes
Yes
Yes
Yes
TB6575B1000 Heat or 
Cool
2
120  or 
240 Vac
4
TB6575C1016 All
2 or 4 120, 240 
or 277 
Vac
5
TB8575A1016 All
2 or 4 24 Vac
5
M27589
UP
5-13/16 (148)
3-13/16
(97)
1-1/8
(29)
THERMOSTAT
SUB-BASE
3-1/4 (83)
2-3/8 (60)
1-3/4
(44)
5/32
(4)
5/32
(4)
1-3/16
(30)