American Water Heater Commercial Ultra Low NOx Gas water Heater User Manual

Page of 24
6
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACK-FLOW
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK 
VALVE, PROVISIONS FOR THERMAL EXPANSION OF WATER IN 
THE HOT WATER SYSTEM MUST BE PROVIDED.
FIGURE 3.
CIRCULATING RETURN LINE CONNECTIONS
TEMPERED WATER LOOP, IF USED, CONNECT TO POINT "A".  
STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO 
COLD WATER INLET
WARNING
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE 
USE TEMPERATURE AT FIXTURES.  SEE TEMPERATURE 
REGULATION ON PAGE 11.  IF HIGHER PREHEAT 
TEMPERATURES ARE NECESSARY TO OBTAIN 
ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD 
VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
SINGLE TEMPERATURE
VENTING
 WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE 
FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION 
OF FLUE GASES.  SUCH CONDITIONS CAUSE SOOTING OR RISKS 
OF FIRE AND ASPHYXIATION.
This water heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will retard 
a free draft.
Type B venting is recommended with these water heaters. 
This water heater must be vented in compliance with all local codes, the 
current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
and with the Category I Venting Tables.
In Canada, venting shall conform to the requirements of the current 
edition of the CAN/CSA B149.1-00 installation code.
If any part of the vent system are exposed to ambient temperatures below 
35 degrees F (2 degrees C) it must be insulated to prevent condensation.
•  Do not connect the heater to a common vent or chimney with solid 
fuel burning equipment.  This practice is prohibited by many local  
building codes as is the practice of venting gas fired equipment to 
the duct work of ventilation systems.
•  Where  a  separate  vent  connection  is  not  available  and  the  vent 
pipe from the heater must be connected to a common vent with an 
oil burning furnace, the vent pipe should enter the smaller common 
vent or chimney at a point above the large vent pipe.
FIGURE 2.
VENT CONNECTION
Vent connections must be made to an adequate stack or chimney. Size 
and install proper size vent pipe.  Do not reduce pipe size to less than 
that of the blower outlet.
Horizontal runs of vent pipe must have a minimum upward slope toward 
the chimney of 1/4 inch per foot (2cm per meter).  Dampers or other 
obstructions must not be installed in between the heater and the blower.  
Be sure that the vent pipe does not extend beyond the inside wall of 
the chimney.
Where a continuous or intermittent back draft is found to exist, the 
cause must be determined and corrected.  A special vent cap may be 
required.  If the back draft cannot be corrected by the normal methods or 
if a suitable draft cannot be obtained, a blower type flue gas exhauster 
must be employed to assure proper venting and correct combustion.
MIXING VALVE APPLICATION FOR TWO TEMPERATURE WATER
VACUUM RELIEF
       VALVE
*INSTALL PER 
LOCAL CODES.