American Water Heater Commercial Ultra Low NOx Gas water Heater User Manual

Page of 24
7
THERMOMETERS (Not Supplied)
Thermometers should be obtained and field installed as shown in 
Figure 3.
Thermometers are installed in the system as a means of detecting the 
temperature of the outlet water supply.
COMBINATION WATER (POTABLE) HEATING 
AND SPACE HEATING
1. All piping components connected to this unit for space heating 
applications shall be suitable for use with potable water.
2. Toxic chemicals, such as those used for boiler treatment, shall 
NEVER be introduced into this system.
3.  This unit may NEVER be connected to any existing heating system 
or component(s) previously used with a non-potable water heating 
appliance.
4.  When the system requires water for space heating at temperatures 
higher than required for domestic water purposes, a tempering 
valve must be installed.  Please refer to installation diagram on 
page 6 of  this manual for suggested piping arrangements.
5.  These water heaters cannot be used in space heating applications 
only.
 CAUTION
A closed system will exist if a check valve (without bypass), pressure 
reducing valve (without bypass), or a water meter (without bypass) 
is installed in the cold water line between the water heater and street 
main (or well).
Excessive pressure may develop in such closed systems, causing 
premature tank failure or intermittent relief valve operation.  This is not a 
warranty failure.  An expansion tank or a similar device may be required 
in the inlet supply line between the appliance and the meter or valve to 
compensate for the thermal expansion of the water.
SYSTEM CONNECTIONS
The system installation must conform to these instructions and to the 
local code authority having jurisdiction.  Good practice requires that all 
heavy piping be supported.
RELIEF VALVE
This water heater is equipped with a combination temperature-pressure 
relief valve that complies with the standard for relief valves for hot water 
supply systems Z21.22-CSA 4.4. 
FOR SAFE OPERATION OF THE 
WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED 
OR PLUGGED.
ASME ratings cover pressure relief capacities. ANSI ratings cover release 
rate with temperature actuation.
In addition to the appliance relief valve, each remote storage tank 
which may be used in conjunction with this appliance shall also be 
installed with a properly sized, rated and approved combination 
temperature (ANSI) and pressure (ASME) relief valve(s). This valve 
shall comply with the standard for relief valves for hot water supply 
systems Z21.22-CSA 4.4.
 
WARNING
THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE 
OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE 
SCALDING  AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER 
DAMAGE.  NO VALVE IS TO BE PLACED BETWEEN THE 
RELIEF 
VALVE AND TANK.
Your local code authority may have other specific relief valve 
requirements.
A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO 
DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR 
WATER DAMAGE.  THIS LINE MUST NOT BE REDUCED FROM THE 
SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES, 
RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS.  
DO NOT THREAD OR CAP THE END OF THIS LINE.  RESTRICTED OR 
BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE 
AND IS UNSAFE.  DISCHARGE LINE SHALL BE INSTALLED TO ALLOW 
COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.
See SERVICE INFORMATION section for procedure and precautions.
The type, size and location of the relief valves must be in accordance 
with local codes.  The location of the relief valve is shown in Figure 1.  
The heater has a factory installed high temperature limit switch.
GAS PIPING
Contact your local gas service company to ensure that adequate gas service 
is available and to review applicable installation codes for your area.
Size the main gas line in accordance with Table 4. The figures shown 
are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is 
considered normal for low pressure systems.  Note:  Fittings such as 
elbows, tees and line regulators will add to the pipe pressure drop.  Also 
refer to the current edition of the National Fuel Gas Code. For Canadian 
installations consult Canadian Installation Code CAN/CSA-B149.1.
 
WARNING
The minimum gas supply pressure for input adjustment is 6.0" kPa W.C. 
for natural gas (11.0" kPa W.C. for propane).
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 
14" kPa WATER COLUMN SUPPLY PRESSURE. EXPOSURE TO HIGHER 
GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE CONTROL 
WHICH COULD RESULT IN FIRE OF EXPLOSION. 
If overpressure has 
occurred such as through improper testing of gas lines or emergency 
malfunction of the supply system, the control must be checked for safe 
operation. Make sure that the outside vents on the supply regulators 
and the safety vent valves are protected against blockage. These are 
parts of the gas supply system not the heater. Vent blockage may occur 
during ice storms.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM 
CONTAMINANTS IN THE GAS WAYS.  SUCH FOULING MAY CAUSE 
IMPROPER OPERATION, FIRE OR EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY 
TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE 
GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY 
LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP 
LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG. 5).  THE 
DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT 
TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH 
RECOMMENDATIONS OF SERVING GAS SUPPLIERS.  REFER 
TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE.  
For Canadian installations consult Canadian Installation Code CAN/
CSA-B149.1.
To prevent damage, care must be taken not to apply too much torque 
when attaching gas supply pipe to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the male threads 
of pipe joints.  Do not apply compounds to the first two threads.  Use 
compounds resistant to the action of liquefied petroleum gases.