13. CHARACTERISTICS
13.5 Inrush Currents at Power-On of Main Circuit and Control Circuit
The following table indicates the inrush currents (measurement data) that will flow when the maximum
permissible voltage (253VAC) is applied at the power supply equipment capacity of 2500kVA and the
wiring length of 10m.
Inrush Currents (Aop)
Servo Amplifier
Main circuit power supply (L1-L3)
Control circuit power supply (L11-L21)
MR-J2S-10CL 20CL
30A
(Attenuated to approx. 5A in 10ms)
MR-J2S-40CL 60CL
30A
(Attenuated to approx. 5A in 10ms)
MR-J2S-70CL 100CL
54A
(Attenuated to approx. 12A in 10ms)
70 to 100A
(Attenuated to approx. 0A in 0.5 to 1ms)
MR-J2S-200CL 350CL
120A
(Attenuated to approx. 12A in 20ms)
100 to 130A
(Attenuated to approx. 0A in 0.5 to 1ms)
MR-J2S-500CL
44A
(Attenuated to approx. 20A in 20ms)
MR-J2S-700CL
88A
(Attenuated to approx. 20A in 20ms)
30A
(Attenuated to approx. 0A in several ms)
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic
contactors. (Refer to Section 14.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be
tripped by an inrush current.