Mitsubishi Electronics MR-J2M-P8A User Manual

Page of 272
5 -  12
5. PARAMETERS
Class No. Symbol
Name and function
Initial
value
Unit
Setting
range
60
LPF
Low-pass filter/adaptive vibration suppression control
Used to selection the low-pass filter and adaptive vibration suppression
control. (Refer to Chapter 7.)
0
Low-pass filter selection
0: Valid (Automatic adjustment)
1: Invalid
When you choose "valid",
2  (1  GD2 setting   0.1)
 VG2 setting   10
bandwidth filter is set automatically.
Adaptive vibration suppression control selection
Choosing "valid" or "held" in adaptive vibration
suppression control selection makes the machine
resonance control filter 1 (DRU parameter No. 58) invalid.
0: Invalid
1: Valid
    Machine resonance frequency is always detected
    and the filter is generated in response to resonance to
    suppress machine vibration.
2: Held
    The characteristics of the filter generated so far are held, 
    and detection of machine resonance is stopped.
Adaptive vibration suppression control sensitivity selection
  Used to set the sensitivity of machine resonance detection.
0: Normal
1: Large sensitivity
[H
z
]
0000
Refer to
Name
and
function
column.
61
GD2B Ratio of load inertia moment to servo motor inertia moment 2
Used to set the ratio of load inertia moment to servo motor inertia moment
when gain changing is valid.
Made valid when auto tuning is invalid.
70
0.1
times
0
to
3000
62
PG2B Position control gain 2 changing ratio
Used to set the ratio of changing the position control gain 2 when gain
changing is valid.
Made valid when auto tuning is invalid.
100
%
10
to
200
63
VG2B Speed control gain 2 changing ratio
Used to set the ratio of changing the speed control gain 2 when gain
changing is valid.
Made valid when auto tuning is invalid.
100
%
10
to
200
64
VICB Speed integral compensation changing ratio
Used to set the ratio of changing the speed integral compensation when
gain changing is valid. Made valid when auto tuning is invalid.
100
%
50
to
1000
Exp
ans
io
DR
U par
ame
te
rs
 2
65
*CDP Gain changing selection
Used to select the gain changing condition. (Refer to Section 7.5.)
0
0 0
Gain changing selection
Gains are changed in accordance with the settings
of DRU parameters No. 61 to 64 under any of the 
following conditions:
0: Invalid
1: Gain changing (CDP    ) is ON
2: Command frequency is equal to higher than
    DRU parameter No. 66 setting
3: Droop pulse value is equal to higher than
    DRU parameter No. 66 setting
4: Servo motor speed is equal to higher than
    DRU parameter No. 66 setting
0000
Refer to
Name
and
function
column.