The Discharge Pipe:
• Shall not be smaller in size than the outlet pipe size of the valve, or 
have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both the 
temperature-pressure relief valve, and the discharge pipe.
• Shall terminate at an adequate drain.
• Shall not have any valve between the relief valve and tank.
The temperature-pressure relief valve must be manually operated at 
least once a year.  Caution should be taken to ensure that (1) no one 
is in front of or around the outlet of the temperature-pressure relief 
valve discharge line, and (2) the water manually discharged will not 
cause any bodily injury or property damage because the water may 
be extremely hot.
If after manually operating the valve, it fails to completely reset and 
continues to release water, immediately close the cold water inlet 
to the water heater, follow the draining instructions, and replace the 
temperature-pressure relief valve with a new one.
GAS PIPING
Make sure the gas supplied is the same type listed on the model rating 
plate.  The inlet gas pressure must not exceed 14 inch  water column (3.5 
kPa) for natural and propane gas (L.P.).  The minimum inlet gas pressure 
shown on the rating plate is that which will permit fi ring at rated input.
All gas piping must comply with local codes and ordinances or with the 
National Fuel Gas Code (ANSI Z223.1/ NFPA-54) whichever applies. 
Copper and brass tubing and fi ttings (except tin lined copper tubing) 
shall not be used.
If the gas control valve is subjected to pressures exceeding 1/2 psi 
(3.5 kPa), the damage to the gas control valve could result in a fi re or 
explosion from leaking gas.
If the main gas line Shut-off serving all gas appliances is used, also turn 
“off” the gas at each appliance.  Leave all gas appliances shut “off” until 
the water heater installation is complete.
A gas line of suffi cient size must be run to the water heater.  Consult the 
current edition of National Fuel Gas Code ANSI Z223.1/NFPA 54 and 
your gas supplier concerning pipe size.
There must be:
•  A readily accessible manual shut off valve in the gas supply line serving 
the water heater, and
•  A drip leg (sediment trap) ahead of the gas control valve to help prevent 
dirt and foreign materials from entering the gas control valve.
• A fl exible gas connector or a ground joint union between the shut off 
valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the water 
heater.  Use a soapy water solution, not a match or open fl ame.  Rinse 
off soapy solution and wipe dry.
Water heaters covered in this manual have been tested and approved for 
installation at elevations up to 7,700 feet (2,347 m) above sea level. When 
installed at elevations above 7,700 feet (2,347 m), input rating should 
be reduced at the rate of 4 percent for each 1,000 feet  (305 m) above 
sea level which requires replacement of the burner orifi ce in accordance 
with National Fuel Gas Code ANSI Z223.1/NFPA  54. Contact your local 
gas supplier for further information.
Failure to replace the standard orifi ce with a high altitude orifi ce when 
installed at elevations above 7,700 feet (2,347 m) could result in improper 
and ineffi cient operation of the appliance, producing carbon monoxide 
gas in excess of safe limits. This could result in serious injury or death. 
Contact your gas supplier for any specifi c changes which may be required 
in your area. 
Use pipe joint compound or tefl on tape marked as being resistant to the 
action of petroleum [Propane (L.P.)] gases.