Start-Up
Analog Inputs
See 
 for a complete description of analog inputs. 
Binary Outputs
Binary outputs are configured to support the following:
Two fan stages (when one or two fan stages are present, J1-2 can be configured as exhaust fan)
One hydronic cooling stage
One hydronic heating stage (dehumidification requires this to be in the reheat position)
One DX cooling stage
One or two-stage electric heat (dehumidification requires this to be in the reheat position)
Face and bypass damper
Modulating fresh air damper (Tracer™ ZN520 only)
One-stage baseboard heat
Table 28. Analog inputs
Analog input
Terminal
Function
Range
ZN010
ZN510
ZN520
Zone
TB3-1
Space temperature input
5° to 122°F (-15° to 50°C)
Ground
TB3-2
Analog ground
N/A
Set
TB3-3
Setpoint input
40° to 115°F (4.4° to 46.1°C)
Fan
TB3-4
Fan switch input
4821 to 4919 W (Off)
2297 to 2342 W (Auto)
10593 to 10807 W (Low)
15137 to 16463 W (High)
Ground
TB3-6
Analog ground
N/A
Analog Input 1
J3-1
Entering water temperature
-40° to 212°F (-40° to 100°C)
J3-2
Analog ground
N/A
Analog Input 2
J3-3
Discharge air temperature
-40° to 212°F (-40° to 100°C)
J3-4
Analog ground
N/A
Analog Input 3
J3-6
Fresh air temp/generic temp
-40° to 212°F (-40° to 100°C)
Analog ground
N/A
Analog Input 4
J3-7
Universal Input
0 – 100%
Generic 4-20 ma
0 – 100%
Humidity
0 – 2000ppm
CO
2
Ground
J3-8
Analog ground
N/A
Ground
J3-9
Analog ground
N/A
Notes:
 1. The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air temperature sensor are 10KW thermistors.
 2. Zone sensor: Wall mounted sensors include a thermistor soldered to the sensor’s circuit board.
 3. Changeover units include an entering water temperature sensor.