Start-Up
Zone Sensor
The Tracer™ ZN controller accepts the following zone sensor module inputs:
Space temperature measurement (10kW thermistor)
Local setpoint (either internal or external on the zone sensor module)
Fan mode switch
Timed override, using “on” and “cancel” buttons (Tracer ZN510 and ZN520 only)
Communication jack (Tracer ZN510 and ZN520 only)
Space Temperature Measurement
Zone sensors use a 10kW thermistor to measure the space temperature. Wall-mounted zone 
sensors include a space temperature thermistor. Unit-mounted zone sensors have a return air 
sensor mounted in the unit’s return airstream. If both a hardwired and communicated space 
Table 29. Binary output configuration
Binary output 
pin connection
Configuration
ZN010
ZN510
ZN520
J1-1
Fan high
J1-2
N/A
J1-3
Fan low
J1-4
(Key)
Fan low
J1-5
Main valve – open, or 2 pos. valve
(a)
(a) Two-pipe hydronic heat/cool changeover units use terminals J1-5 and J1-6 to control the primary valve for both heating and
cooling. Units configured and applied as 2-pipe hydronic heat/cool changeover with electric heat, use terminals J1-5 and
J1-6 to control the primary valve (for both cooling and heating), and terminals J1-9 and J1-10 for the electric heat stage.
For those 2-pipe changeover units, electric heat will not energize while the hydronic supply is hot (5 or more degrees
above the space temperature). In a 4-pipe application, pin J1-5 is for cooling and pin J1-6 for heating.
J1-6
Aux. valve/elec. ht.
Aux. valve – close
J1-7
2-pos. damper
J1-9
Heat valve – open, or 2 pos. valve, or first stage elec. ht.
J1-10
Heat valve – close or sec. stage elec. ht.
J1-11
Fresh air damper – open
J1-12
Fresh air damper – close
TB4-1
Generic / baseboard heat output
TB4-2
24 VAC
Notes:
 1. If no valves are ordered with the unit, the factory default for Tracer™ ZN010 and ZN510 controllers are: main valve 
configured as normally closed and aux. valve configured as normally open.
 2. If the fresh air damper option is not ordered on the unit, 2-pos. damper is configured as none.
 3. Pin J1-2 can be configured for an exhaust fan with the use of Rover™ software. Factory default is none.
Table 30. Zone sensor wiring connections
TB1
Description
1
Space  temperature
2
Common
3
Setpoint
4
Fan  mode
5
Communications
6
Communications