Black Box MPSH16-D20-120V User Manual

Page of 193
CHAPTER 1:  Specifications
 
13
1.  Specifications
Physical/Environmental:
Models MPSH8-S20-120V, MPSH8-S20-208+V,  MPSH8-D20-120V and 
MPSH8-D20-208+V:
Width:  19”  (48.3 cm) (Including Rack Brackets)
Depth:  8.7”  (22.1 cm)
Height:  1.75”  (4.5 cm) One Rack U
Models MPSH16-D20-120V, MPSH16-D20-208+V:
Width:  19”  (48.3 cm) (Including Rack Brackets)
Depth:  8.7”  (22.1 cm)
Height:  3.5”  (8.9 cm)  Two Rack U
Operating Temperature:  32˚F to 122˚F (0˚C to 50˚C)
Humidity:  10 - 90% RH
Operating Temperature:  32˚F to 122˚F (0˚C to 50˚C)
Humidity:  10 - 90% RH
Network Interface:  10/100Base-T Ethernet, RJ45, multi-session Telnet.
Power Outlets:
MPSH8-S20-120V:  Eight (8) each, NEMA 5-15R Outlets.
MPSH8-S20-208+V:  Eight (8) each, IEC320-C13 Outlets.
MPSH8-D20-120V:  Eight (8) each, NEMA 5-15R Outlets.
MPSH8-D20-208+V:  Eight (8) each, IEC320-C13 Outlets.
MPSH16-D20-120V:  Sixteen (16) each, NEMA 5-15R Outlets.
MPSH16-D20-208+V:  Sixteen (16) each, IEC320-C13 Outlets.
Power Requirements and Maximum Load:
 
Model No.
Input 
Feeds
Input 
Voltage
Max. Load 
per Outlet
Max. Load 
per Input
Max. Load 
per Unit
MPSH8-S20-120V
1 ea, 20 Amp 100 to 120 VAC
12 Amps
16 Amps*
16 Amps*
MPSH8-S20-208+V
1 ea, 20 Amp 100 to 240 VAC
10 Amps
16 Amps*
16 Amps*
MPSH8-D20-120V
2 ea, 20 Amp 100 to 120 VAC
12 Amps
16 Amps*
32 Amps*
MPSH8-D20-208+V
2 ea, 20 Amp 100 to 240 VAC
10 Amps
16 Amps*
32 Amps*
MPSH16-D20-120V
2 ea, 20 Amp 100 to 120 VAC
12 Amps
16 Amps*
32 Amps*
MPSH16-D20-208+V
2 ea, 20 Amp 100 to 240 VAC
10 Amps
16 Amps*
32 Amps*
*  In accordance with UL requirements, this value has been de-rated to 80%.