OUTLET MANAGED PDU
 
158
13.5.  Viewing Outlet Managed PDU Status via SNMP
Status of various components of the Outlet Managed PDU can be retrieved via 
SNMP.  Plug Status, and Environmental Status are currently supported.
13.5.1.  Plug Status
The status of each plug in the system can be retrieved using the command below.
• 
plugTable::plugStatus – The status of the plug.
 
0 – Plug is OFF
 
1 – Plug is ON
• 
plugTable::plugName - String indicating the plug’s user-defined name.
13.5.2.  Unit Environment Status
The environment status can be retrieved for various variables for all of the Outlet 
Managed PDUs in the system.  The environmentUnitTable contains four rows, one 
row for each unit in the system (LOCAL, AUX1, AUX2, AUX3.)
• 
environmentUnitTable::environmentUnitName – The unit 
(LOCAL.)
• 
environmentUnitTable::environmentUnitTemperature – 
The temperature of the given unit.
• 
environmentUnitTable::environmentUnitCurrentA – Unit’s 
total current for Branch A.  Note that Current will be reported in tenths of an 
Amp (divide result by ten to determine value in Amps.)
• 
environmentUnitTable::environmentUnitVoltageA – Unit 
voltage for Branch A
• 
environmentUnitTable::environmentUnitPowerA – Power 
drawn by Branch A
• 
environmentUnitTable::environmentUnitCurrentB – Unit’s 
total current for Branch B.  Note that Current will be reported in tenths of  
an Amp.
• 
environmentUnitTable::environmentUnitVoltageB – Unit 
voltage for Branch B
• 
environmentUnitTable::environmentUnitPowerB – Power 
drawn on Branch B
• 
environmentMonthlyPowerLog - The monthly power usage log.