Figure 17: Manual Reset Limit Switch
12.3 Lighting Instructions 
12.3.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to 
the heater are on. Check that the on site 
controls are "ON".
IMPORTANT: The thermostat setting must be above 
the ambient temperature for the heater to operate.
2. The automatic firing sequence will begin as 
described 
on Page 27, Figure 15. The heater 
will now operate automatically under the control 
of the on site controls.
12.3.2 To Turn Heater Off 
Set the thermostat to the "OFF" position.
The burner will turn off immediately.
To restart, turn the thermostat above room 
temperature.
12.4 Simple Troubleshooting
Some possible reasons for the heater not operating 
are:
1. Gas supply not "ON".
2. Electricity supply not "ON".
3. The time and/or temperature controls are not 
"ON".
4. A limit switch may have operated. This may be 
caused by an interruption of the electrical 
supply, failure of the distribution fan or vent or 
heat exchanger blockage.
If a temperature limit switch persistently trips, there 
is a fault which must be investigated by a contractor 
qualified in the installation and service of gas-fired 
heating equipment.
12.4.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry 
for ignition (four trials total). After four unsuccessful 
ignition trials, the control will put the heater into 
lockout for one hour.
Lockout should not occur during normal operation of 
the heater and indicates there is a fault condition 
which must be corrected. There is an LED light on 
the ignition control that flashes codes to assist in 
fault correction. 
See Page 30, Figure 18 for LED 
indication codes.
Figure 18: LED Diagnostic Codes
Reset Button
To reset manual reset limit switch, press reset 
button. NOTE: To reset, the switch must be cool.
Description
Part Number
Manual Reset Limit Switch
90412106
LED INDICATION FAULT MODE
Slow Flash
Normal Operation - No call for heat.
Fast Flash
Normal Operation - Call for heat.
2 Flashes
Ignition Lockout - No flame detected.
3 Flashes
Airflow Fault - Pressure switch open or closed.
4 Flashes
Temperature Limit or 
Manual Reset Limit Switch Open
5 Flashes
Flame Sense Error - Gas valve not energized.
Steady On
Internal Control Failure