Honeywell 6039 User Manual

Page of 24
 
 
7
Use a NEMA L14-30 plug with this receptacle (rotate to lock/
unlock). Connect a suitable 4-wire grounded cord set to the plug 
and to the desired load. The cord set should be rated for 250 Volts 
AC at 30 Amps (or greater) (Figure 7).
Figure 7 - 120/240 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase 
loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps or 
240 Volt AC, 60 Hz, single phase loads requiring up to 7200 watts 
(7.2 kW) of power at 30 Amps. The outlet is protected by a 2-pole 
toggle switch circuit breaker.
If there are any problems operating the generator, please call the 
generator helpline at 1-855-GEN-INFO.
Never operate in an enclosed area or indoors! 
NEVER use in the home, in a vehicle, or in 
partly enclosed areas such as garages, EVEN 
IF doors and windows are open! ONLY use 
outdoors and far from open windows, doors, 
vents, and in an area that will not accumulate 
deadly exhaust.
The engine exhaust fumes contain carbon 
monoxide, which you cannot see or smell. 
This poisonous gas, if breathed in sufficient 
concentrations, can cause unconsciousness or 
even death.
Adequate, unobstructed flow of cooling and 
ventilating air is critical to correct generator 
operation. Do not alter the installation or permit 
even partial blockage of ventilation provisions, 
as this can seriously affect safe operation 
of the generator. The generator MUST be 
operated outdoors.
This exhaust system must be properly 
maintained. Do nothing that might render the 
exhaust system unsafe or in noncompliance 
with any local codes and/or standards.
Always use a battery operated carbon 
monoxide alarm indoors, installed according to 
the manufacturers instructions.
The generator has a system ground that connects the generator 
frame components to the ground terminals on the AC output 
receptacles.  The system ground is bonded to the AC neutral wire 
in the generator control panel via a jumper wire.
There may be Federal or State Occupational Safety and Health 
Administration (OSHA) regulations, local codes, or ordinances that 
apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or the 
local agency having jurisdiction:
• In some areas, generators are required to be registered with 
local utility companies.
• If the generator is used at a construction site, there may be 
additional regulations which must be observed.
Connections for standby power to a building’s electrical system 
must be made by a qualified electrician.  The connection must 
isolate the generator power from utility power or other alternative 
power sources and must comply with all applicable laws and 
electrical codes.
A  3-POLE  TRANSFER  SWITCH  MUST  BE  USED  WITH  THIS 
GENERATOR. A 2-POLE TRANSFER SWITCH WILL NOT WORK 
BECAUSE THE NEUTRAL WIRES ARE BONDED TO GROUND.
The National Electrical Code requires that the frame and 
external electrically conductive parts of this generator be 
properly connected to an approved earth ground (Figure 8)
Local electrical codes may also require proper grounding of the 
unit. For that purpose, connecting a No. 10 AWG (American Wire 
Gauge) stranded copper wire to the grounding lug and to an 
earth-driven copper or brass grounding rod (electrode) provides 
adequate protection against electrical shock. However, local codes 
may vary widely. Consult with a local electrician for grounding 
requirements in the area.
Operation