page 24 — DCa40sskU/kU4i 60 hz generaTor • operaTion anD parTs manUal — rev. #1 (03/11/13) 
GeneratOr Outputs
generaTor oUTpUT volTages 
A wide range of voltages are available to supply voltage for 
many different applications. Voltages are selected by using 
the 
voltage selector switch (Figure 13). To obtain some of 
the voltages as listed in  Table 7 (see below) will require a 
fine adjustment using the 
voltage regulator (VR) control 
knob located on the control panel. 
voltage selector switch
The voltage selector switch (Figure 13) is located above 
the output terminal panel’s Hard Wire Hook-up Panel. It 
has been provided for ease of voltage selection.
Figure 13. Voltage Selector Switch
voltage selector switch locking Button
To lock the voltage selector switch, 
press and hold the 
red  button  located  at  the  bottom  of  the  switch. While 
holding the red button down, insert a pad lock into the hole 
next to the button to retain it in the inward locked position. 
When the lock is removed, the red button is spring loaded 
and will return to its normal outward unlocked position.
  CaUTion
never change the position of the voltage selector 
switch while the engine is running. alWaYs place 
circuit  breaker  in  the 
oFF  position before  selecting 
voltage
.
Table 7. voltages available
UvWo output 
Terminal lugs
voltage selector switch
3-phase 240/139v position
voltage selector switch
3-phase 480/270v position
 
line-line
208V
220V
240V
416V
440V
480V
1Ø 
line-neutral
120V
127V
139V
240V
254V
277V
voltage selector switch single-phase 240/120v position
1Ø 
line-neutral/
line-line
120V 
Line-Neutral
N/A
N/A
240V 
Line-Line
N/A
N/A
generator amperage
Table  8  shows  the 
maximum  amps  the  generator  can 
provide. 
Do noT exceed the maximum amps as listed..
gFCi receptacle load Capability
The  load  capability  of  the  GFCI  receptacles  is  directly 
related to the voltage being supplied at either the output 
terminals or the 2 twist lock auxiliary receptacles.
Table  9  and Table  10  show  what  amount  of  current  is 
available at the GFCI receptacles when the output terminals 
and twist lock receptacles are in use. Be careful that your 
load does not to exceed the available current capability at 
the receptacles.
Table 8. generator maximum amps
rated voltage
maximum amps
1Ø 120 Volt
82 amps (4 wire) 
89A x 2 (Zigzag)
1Ø 240 Volt
41 amps (4 wire) 
89A (Zigzag)
3Ø 240 Volt
89 amps
3Ø 480 Volt
44 amps
Table 9.  1Ø gFCi receptacle load Capacity
kW in Use 
Twist lock (C6369)
available load 
Current (amps)
1Ø 240/120V
GFCI Duplex 
5-20R 120V
21.0
0
19.8
5 amps/receptacle
18.6
10 amps/receptacle
17.4
15 amps/receptacle
16.2
20 amps/receptacle
Table 10.  3Ø generator maximum amps
kva in Use 
(UvWo Terminals)
available load 
Current (amps)
3Ø 240/480V
GFCI Duplex 
5-20R 120V
37
0 amps/receptacle
32.8
5 amps/receptacle
28.7
10 amps/receptacle
24.5
15 amps/receptacle
20.4
20 amps/receptacle